H7 ASD Operation Manual
Appendix E
205
Appendix E
Cable/Terminal Specifications
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the ASD.
Table 14. 230 Volt Drive Cable/Terminal Specifications.
Model
VT130H7U
Circuit
Breaker
Rating
(Amps)
Typical Wire/Cable Size (AWG)
Lug Size
Input/Output
Power
AM, FM, and II
Terminals
Control Terminal
Strip
ASD Input/Output Power
Lug Wire Capacity
2010
15
#14
#20
(3-core shield)
#18
(2-core shield)
8 to 24 AWG
2015
15
#14
2025
15
#14
2035
20
#14
2055
30
#14
2080
50
#10
2110
70
#8
2160
90
#6
2220
100
#4
14-1/0
2270
125
#4
2330
150
#3
www
. ElectricalPartManuals