120
4400 Series Installation and Operation Manual – 64527-008
TOSHIBA
4400 UPS
Installation Planning Guide for
15-100kVA UPS
Standard System: 208/120V Input, 208/120V Output
Rev.
1
.6
Page 3 of 3
4400-
IPG
-208/120v-208/120V
Important Notes:
1.
Maximum Current required at Primary AC Input based on full load output and maximum battery charging
current.
2.
Output load conductors are to be installed in separate conduit from input conductors.
3.
Control wires and power wires are to be installed in separate conduits.
4.
Recommended AC input and output overcurrent protection based on continuous full load current per NEC
215.3.
5.
Wiring shall comply with all applicable national and local electrical codes.
6.
Grounding conductors to be sized per NEC Article 250
-
122. Neutral conductors to be sized per NEC Article
310.15.
Primary & optional Secondary AC Input: 3
, 4-
wire + ground.
AC Output: 3
, 4-
wire + ground.
DC Input: 2-
wire (Positive/Negative) + ground.
7.
Nominal battery voltage based on the use of VRLA type batteries (2.0 volts / cell nominal).
8.
Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC.
9.
DC Circuit Breaker size based on breakers external to Toshiba
-
supplied Battery Cabinet(s) or UPS(s).
(NOTE: Toshiba-supplied Battery Cabinets come equipped with internal circuit breakers sized to
meet specific operating conditions)
10.
DC wires should be sized to allow not more than a 2
-
volt drop at maximum discharge current.
11.
Weights do not include batteries or other auxiliary equipment external to the UPS.
12.
Sizing calculations based on the following assumptions:
3-Phase/3-
Wire + Ground: Ref.
2014 NEC Handbook
, Table 310.15(B)(16)
for 75 °C conductors
.
3-Phase/4-
Wire + Ground:
Not more than 9 current-carrying conductors installed in steel conduit in
ambient temperature of 40°
C.
(Ref. NEC Handbook, Table 310.15(B)(2)(a) and Table 310.15(B)(16))
Temperature rating of copper conductors and terminals: 75°
C.
Feeder distance calculations based on NEC Chapter 9, Tables 8 and 9 data, allowing for 2% AC voltage
drop.
NOTE: Consult latest edition of applicable national and local codes for possible variations.
Ratings of wires and overcurrent devices are suggested minimums
. Local conditions may vary. Consult with a
registered Professional Engineer within your local
area for proper size selections.
TOSHIBA
INTERNATIONAL CORPORATION
SOCIAL INFRASTRUCTURE SYSTEMS GROUP
POWER ELECTRONICS DIVISION
13131 West Little York Road
Houston, TX 77041
Telephone: 855-803-7087
Fax: 713-
896
-5212
https://www.toshibaUPS.com
Summary of Contents for 4400 Series
Page 2: ......
Page 6: ...This page left intentionally blank ...
Page 10: ...This page left intentionally blank ...
Page 136: ...This page left intentionally blank ...
Page 137: ......