4400 SPECIFICATIONS: 50kVA w/ Internal Battery Backup
Specification
50kVA
Enclosure
NEMA 1
Construction
Welded Steel Chassis
Color
Powder Coat, DuPont O’Brien Black
Emergency Power Off (EPO)
Yes
Control Panel
Touchscreen and LED
MONITORING
Operator Interface (Front Panel)
Touchscreen and LED
Dry Contacts Included
Yes
RS-232 Interface
Yes
Optional – Intelligent Monitoring
Yes –
RemotEye 4
Optional – Remote Status Alarm Panel (RSAP)
Yes
ADDITIONAL FEATURES
Optional Matching Battery Cabinets
Yes
Optional Matching MBS/PDU Cabinet
Yes
OTHER
Warranty (yr.)
3 Years
Certifications
UL 1778, CUL, NEC (NFPS-70), CE, IBC, CBC, ANSI C62.41 (IEEE
587), Nema/PET-1993, OSHA, ISO9000, ISO 14001:2004.
11.7 Estimated Runtime on Internal Batteries – 50kVA
Below are charts of the estimated runtime for the 4400 Series 50kVA on internal batteries at various loads at a 0.9 and 0.8 Power Factor.
The 80-100kVA UPS is not available with internal batteries. An external battery cabinet (or equivalent) is required to provide backup power.
These runtimes are estimates based on new batteries operating at 76 °F. Actual runtimes may vary due to manufacturing variations, previous discharge
profiles, battery age, and operating temperature.
ESTIMATED RUNTIME ON INTERNAL BATTERIES AT VARIOUS LOADS
1
UPS
Estimated Runtime in Minutes at Percent Full Load
1
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
50kVA (0.8 PF)
>60
>60
>60
50
37
29
24
19
17
14
50kVA (0.9 PF)
>60
>60
>60
42
32
25
19
17
14
12