84
4400 Series Installation and Operation Manual – 64527-008
RUN/STOP Button Operation
Operation of the RUN/STOP button:
When the UPS is in BYPASS mode, the RUN button is dis-
played.
1.
To switch the UPS to In-Line operation, press the RUN
button.
2. The RUN icon changes to an Hourglass for 3 seconds.
The control button is disabled while the hourglass is
displayed.
The same delay occurs when switching from RUN to
STOP.
3.
After the hourglass icon clears the STOP icon is dis-
played. The UPS is in In-Line mode.
4.
To put the UPS back into Bypass mode, press the STOP
button. The hourglass will display as in step 2, then the
button will display the RUN icon.
4400F3F300FAB 30KVA
2013012345
4400F3F300FAB 30KVA
2013012345
4400F3F300FAB 30KVA
2013012345
FIGURE 12.11: RUN/STOP BUTTON
OPERATION
Summary of Contents for 4400 Series
Page 2: ......
Page 6: ...This page left intentionally blank ...
Page 10: ...This page left intentionally blank ...
Page 136: ...This page left intentionally blank ...
Page 137: ......