16
Verify the motor rotation to ensure that the pump is turning in the right direction. The START and STOP push
buttons can be used to toggle the motor ON/OFF.
WARNING!
On a Wye-Delta closed transition starter, if the transition from Wye to Delta occurs (after 5 to 8 seconds depending
on the motor HP), the manual stop push button will be disabled for 80 seconds. To stop the engine before the end
of the 80 second delay, use the disconnecting mean handle.
Summary of Contents for GPU
Page 20: ...20 The First Start up is now completed The controller is fully installed and configured ...
Page 45: ...45 The Sensors Pages ...
Page 52: ...52 ...