63
6)
If 00-
ERR (or “I/O Board Com: ERR”) appears, verify the communication parameters for Com0
within the Communication Setup Menu. This menu is located under the Configuration Menu. The
Com0 communication settings required for the I/O board are .57.6 (K Baud), None (Parity), 8 Data
(bits), 1 Stop (bit), Single, and I/O Board (type of serial device). This is correctly set in the factory
when an RCU II is assembled, but it is possible for the settings to be updated by the installer.
Using I/O Diagnostics
6.7
MultiLoad II:
Consult the MultiLoad II User Manual for diagnostics functions.
RCU II:
Each output is listed on the screen, adjacent to a number. Press a number on the keypad that
corresponds to the output under test. If the connection has been made properly, the field device will
actuate.
NOTE
:
If numbers do not appear next to the outputs, enter
Configurations
RCU Setup
and
change the password from the default “
00000
”.
Inputs
: Each input is listed on the screen adjacent to its status. Each input will be in either the ON or
OFF state. Activate each input from the field. If the circuit is connected properly, the state change can
be observed.
For the counter inputs, the totals will accrue as long as they are receiving pulses (
MultiLoad II/ RCU
II):
Summary of Contents for MultiLoad II DIV-2
Page 1: ...MultiLoad II RCU II DIVISION 2 DIV2 Installation Guide Part 6074...
Page 7: ...Hardware Revision 80 9 1 Manual Revision 81 9 2...
Page 20: ...11 2 1 2 4 Side View Figure 2 6 Unit Outline Drawing Side View...
Page 25: ...16 Figure 3 1 Suggested Mounting Position Figure 3 2 Screen Visible Area...
Page 59: ...50 Typical 1 Meter Application Wiring Example IP E Drawing Electrical Wiring Schedule 5 4 14...
Page 64: ...55...
Page 73: ...64...
Page 88: ...79 Chapter8 HardwareRevisionHistory Compatibility Chapter 8...