21
Available Communications Protocol Selection and Wire Spec
4.1
This section describes the available communication protocols for MultiLoadII/RCU II.
RS-422/485
4.1.1
The RS-422/485 communications protocol is designed for multi-point (i.e. computer to multiple
devices, also called multi-dropped) communications up to 4,000 feet (1,220 Meters).
RS-422 requires 4-wires (2 twisted pair) for full duplex communications and utilizes a transmit pair
of wires (TDA & TDB) and a receival pair of wires (RDA & RDB).
RS-485 requires 2-wires (1 twisted pair) for half duplex communications and utilizes a single pair
of wires (TDA/RDA & TDB/RDB) for transmittal and receival
This manual will typically refer to both RS-422 and RS-485 as simply RS485 2 Wire or RS485 4
Wre.
Although a ground wire is not required, the common mode voltage between the MultiLoad
II/ RCU II and the field device must be within -7Vdc to 12Vdc. To correct situations
where this is not the case, the DC common is available on COM 0 and COM 1 by using
TB2, pin five (revision 1.1 Power Supply/Comm boards only) and TB 3, pin three.
Connect the MultiLoad II/ RCU II DC common to the signal ground of the field device.
Wire used must meet the following characteristics:
-
24 AWG stranded.
-
4-wire, two twisted pair with overall shield.
-
2-wire, one twisted pair with overall shield.
-
30 pF maximum between conductors.
-
1,000 ohm impedance.
-
Maximum length: 4,000 feet (1,220 Meters).
-
Maximum stub length: 15 feet.
All exposed shields must be properly insulated to prevent short circuits.
All shields must be continuous, soldered, and properly insulated.
RS-232
4.1.2
The RS-232 protocol is designed for point-to-point (i.e., computer to a single device)
communications limited to 50 feet requiring a minimum of 3 wires: transmit, receive and ground.
Additional wires are required for hardware handshaking when using printers and data loggers.
Wire used must meet the following characteristics:
-
24 AWG.
-
3 conductor with overall shield (data only) or 8 conductor with overall shield (full
handshaking).
Summary of Contents for MultiLoad II DIV-2
Page 1: ...MultiLoad II RCU II DIVISION 2 DIV2 Installation Guide Part 6074...
Page 7: ...Hardware Revision 80 9 1 Manual Revision 81 9 2...
Page 20: ...11 2 1 2 4 Side View Figure 2 6 Unit Outline Drawing Side View...
Page 25: ...16 Figure 3 1 Suggested Mounting Position Figure 3 2 Screen Visible Area...
Page 59: ...50 Typical 1 Meter Application Wiring Example IP E Drawing Electrical Wiring Schedule 5 4 14...
Page 64: ...55...
Page 73: ...64...
Page 88: ...79 Chapter8 HardwareRevisionHistory Compatibility Chapter 8...