PWi Forging User’s Manual
Doc #17663 Rev A Page
Toledo Integrated Systems
60
E-Stop Menu
The E-Stop menu configures the operation of the Emergency Stop (E-Stop)
shutdown relay. See page 25 for E-Stop relay location and wiring.
Description of Emergency Stop relay operation
When E-Stop is set to “OFF”:
All alarms, including capacity alarms, cause the Top-Stop relay to open at the end
of the stroke.
The E-Stop relay has no function.
When E-Stop is set to “CAP ALARM”:
Capacity alarms cause the E-Stop relay to open immediately when an over-capacity
load occurs. This also applies to CCM alarms if the optional resolver board is
installed.
Warning:
Using the E-Stop relay under heavy loads may result in the ram
becoming locked at the bottom of stroke. If this is a concern, the E-Stop relay
should not be used.
The Top-Stop relay will open for high, low, and reverse setpoint violations.
To change the E-Stop relay operation
1)
Push
to enter change mode. Current setting is then selected.
2)
Push
or
to change the setting.
3)
Push
to accept the change, or push
to cancel the change.
Summary of Contents for PWi Forging
Page 1: ...17664 PWi Forging Tonnage Monitor By Toledo Integrated Systems User s Manual...
Page 2: ......
Page 28: ...PWi Forging User s Manual Doc 17663 Rev A Page Toledo Integrated Systems 26...
Page 74: ...PWi Forging User s Manual Doc 17663 Rev A Page Toledo Integrated Systems 72...
Page 78: ...PWi Forging User s Manual Doc 17663 Rev A Page Toledo Integrated Systems 76...
Page 80: ......
Page 82: ...Doc 11080 Rev A T400 INSTALLATION PAGE 2...
Page 83: ...Doc 11080 Rev A T400 INSTALLATION PAGE 3...
Page 84: ...Doc 11080 Rev A T400 INSTALLATION PAGE 4...
Page 87: ...Doc 11080 Rev A T400 INSTALLATION PAGE 7...
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......