Protocol-specific data
HART
Manufacturer ID
0x11
Device type ID
0x0038
HART protocol revision
7
Device description files
(DTM, DD
)
Consult TLV for more information.
HART load
• Min. 250 Ω
• Max. 500 Ω
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (U
S
), the maximum load (R
B
) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage
• For U
S
= 17.9 to 18.9 V: R
B
侑 (U
S
- 17.9 V): 0.0036 A
• For U
S
= 18.9 to 24 V: R
B
侑 (U
S
- 13 V): 0.022 A
• For U
S
= 侒 24 V: R
B
侑 500 Ω
0
100
200
300
400
500
16
18
20
22
24
26
28
30
32
U [V]
S
R
B
[Ω]
34
36
A0013563
Operating range
Sample calculation
Supply voltage of power supply unit: U
S
=19 V
Maximum load: R
B
侑 (19 V - 13 V): 0.022 A = 273 Ω
Low flow cut off
The switch points for low flow cut off are preset and can be configured.
Galvanic isolation
All inputs and outputs are galvanically isolated from one another.