Local display
Plain text display
With information on cause and remedial measures
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
• HART protocol
• Via service interface
CDI service interface
Plain text display
With information on cause and remedial measures
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure mode
Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode
No pulses
Frequency output
Failure mode
Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1
250 Hz
Switch output
Failure mode
Choose from:
• Current status
• Open
• Closed