The effective upper range value Q
High
is determined using the smallest of the three values Q
max
,
Q
AmpMax
and Q
Ma=0.3
.
Q
[m /h] = min
High
³
Q
[m /h]
max
³
Q
[m /h]
AmpMax
³
Q
[m /h]
Ma = 0.3
³
High
³
Q
[ /min]
max
Q
[ /min]
AmpMax
Q
[ /min]
Ma = 0.3
A0034338
Q
High
Effective upper range value
Q
max
Maximum measurable flow rate
Q
AmpMax
Maximum measurable flow rate based on signal amplitude
Q
Ma = 0.3
Restricted upper range value is dependent on Mach number
For liquids, the occurrence of cavitation may also restrict the upper range value.
Operable flow range
The value, which is typically up to 49: 1, may vary depending on the operating conditions
(ratio between upper range value and lower range value)
Output
Output signal
Current output
Current output 1
4-20 mA (passive)
Resolution
< 1 µA
Damping
Adjustable: 0.0 to 999.9 s
Assignable measured
variables
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam pressure
• Total mass flow
• Energy flow
• Heat flow difference
Input signal
Integrated pressure and temperature measurement
The measuring device can also directly record external variables for density and energy
compensation.
• Measurement of pressure, temperature and flow in a true 2-wire version
This product version offers the following benefits:
• Recording of pressure and temperature at the same point, thus ensuring maximum accuracy
of density and energy compensation
• Easy testing of pressure measurement accuracy:
• Application of pressure by pressure calibration unit, followed by input into measuring device
• Automatic error correction performed by device in the event of a deviation
• Availability of calculated line pressure.