background image

14

RELAY

RELAY MODE:

 If the relay is required for a flow switch 

check the flow switch box and a further set of options 
for set point and hysteresis will appear. 

THRESHOLD:

 

Set the required flow rate for the flow 

switch. The 

Reset Offset (%)

 (Hysteresis) is either 

negative or positive depending on whether a falling 
or rising alarm is required. The relay has change over 
contacts but to reduce power consumption the relay 
is off if positive hysteresis is selected and only powers 
when the threshold is exceeded. If negative hysteresis 
is chosen the relay is on up to the set point. The 
increments are preset and can be cycled through using 
the + &- buttons. If more than one set point is required 
either both transistors must be used or one transistor 
and the relay.

ANALOGUE OUTPUTS

ANALOGUE MODE:

 

There are four options on the 

drop down menu: Not Used, 4-20mA, 0-5 Volt and 
0-10 Volt.

Once the selection has been made you can enter the 
low and high flows for the analogue outputs as required. 
These are numeric entries in the units and time base 
selected in calibration settings.

Summary of Contents for Atrato 710

Page 1: ...INSTRUCTION MANUAL Ultrasonic Flowmeter Range TM B r e a k t h r o u g h F l o w m ete r T e c h n o l o g y...

Page 2: ...TM...

Page 3: ...1 General 4 2 Installation 5 3 Electrical 6 4 Setup 7 5 Technical Specification 21 CONTENTS Page No...

Page 4: ...General 4 First 3 digits Flow range 710 2 500 mL min 720 0 01 1 7 L min 740 0 02 5 L min 760 0 1 20 L min Fourth digit seal material V Viton N Nitrile E EPDM S Silicon Fifth digit end fittings 0 3 8...

Page 5: ...on the flowmeter to keep any gas in solution We recommend 500mbar plus two times the fluid vapour pressure If there is any chance of air passing through the system mount the Atrato in a vertical pipe...

Page 6: ...re conductors are clear of the surface of the connector strip prior to closing the housing 3 Electrical Atrato Connector Assignments Pin No Label Function 1 Relay NO Isolated relay contact normally cl...

Page 7: ...ions of the panel on the top left of the screen Control buttons to apply the settings and recover previously set parameters 4 Setup 7 Send settings to system Retrieve Settings from meter Open settings...

Page 8: ...bs whilst adjusting the User Settings The Flow Details window may be further reduced or expanded using the minimise and maximise icons respectively in the top right hand of the window USER SETTINGS TA...

Page 9: ...ill not give outputs Display Mode The down arrow selects from the various display and Metraflow functions The options are Rate The display will show flow rate only Total The display will show total fl...

Page 10: ...ppropriate terminal for each action The options are Not used Output Input PIN 7 NPN Pin 7 can be configured as either an output or an input but not both simultaneously If one input and one output is r...

Page 11: ...dance with the user set Hysteresis High Threshold will cause an alarm signal to Latch on when flow is seen above the set value Low Threshold will cause an alarm signal to Latch on when flow is seen be...

Page 12: ...or Reset Alarm can be operated remotely by using a switch and resistor to apply a suitable voltage between 5 and 24 Vdc to either Pin 6 or Pin 7 as described on page 13 This option allows the user to...

Page 13: ...rent cannot exceed 5mA An example circuit is given below Example Input to Pin 7 Pin 6 In input mode the PNP open collector output is disabled and the input pin responds to an external input voltage at...

Page 14: ...ve hysteresis is selected and only powers when the threshold is exceeded If negative hysteresis is chosen the relay is on up to the set point The increments are preset and can be cycled through using...

Page 15: ...to Output and set to Flow switch the Value column will show the transistor status either low or high and the notes will show the selected switch points OR If Output and Reverse Flow are selected the...

Page 16: ...tab selected Low Input logic level Left push button selected will momentarily show high when remotely operated Low Input logic level Right push button selected will momentarily show high when remotel...

Page 17: ...by pressing the right hand button in the paused state a further press of the right button cancels the batch If you wish to continue the batch from the paused state the left hand button continues the...

Page 18: ...he PIN protection To use these features it is first necessary to create a PIN This is a four digit number in the range 0001 to 9999 Setting a value of 0000 tells the software there is no PIN and this...

Page 19: ...nd the user can click the FASTER button to adjust the measurement window a stronger signal point A RED graphic is a very poor signal ORANGE indicates a weak signal and GREEN is a Good strong signal Th...

Page 20: ...rameter you wish to log choose a sensible sampling period i e for longer data logging periods choose 10 second intervals to limit the size of the file created and then click the Icon under Storage Fil...

Page 21: ...ed 10K ohm LCD display Reflective 6 x 8mm high main characters 2 5mm enunciators Gal cc Kg gms Ltr min Hr Sec 4 20mA output into 250 ohm maximum 14 bit resolution 0 1 linearity plus flowmeter accuracy...

Page 22: ...TITAN ENTERPRISES LTD Coldharbour Business Park Sherborne Dorset DT9 4JW Phone 44 0 1935 812790 Email sales atratoflowmeters com www atratoflowmeters com Distributed by 01 19 1...

Reviews: