Increase the timing(hour) set(00 to 24)
-
Adjust different setting values at different states
5
、
Decrease the humidity value set(RH10% to 95%)
6
、
Decrease the timing(hour) set(00 to 24)
Timing
Short press the button to launch a cycle of
Set on/off Timer and Exit
Function Description
1. Humidity Control
When room humidity value 3% lower than set, compressor shut down, fan delay 3 minutes and
shut down; and when it's 3% higher than the humidity value set, both fan and compressor operate.
Note
◆
When the humidity is set at the minimum value, it’s defaulted to enter the continuous
dehumidifying mode
◆
Upon fault of the humidity sensor, it turns to the continuous dehumidifying mode
◆
Upon fault of the coil sensor, it turns to the timing defrosting mode(See the defrosting mode)
◆
When it’s shut down, the fan will be closed 10s later.
2. Protection Function
◆
Once shut down, the compressor takes 3min to start. Quick start is available for the first
power-on.
◆
Power off memory: For abrupt power outage or accidental unplugging of the plug, the system
will automatically archive the operating state right before the incident, and continue at that state for
the next power-on.
◆
Full water protection: When the water tank is full, the dehumidifier automatically shuts down and
enters the standby state, the indicator light “Full Water” on and buzzer alarms.