Biofell Cascade
601130040 [Revision 1502.00] [subject to changes with no previous notice]
Page 17 of 20
1320
E-F
Heating curve slope
1.5
0.10
4.00
0.10
1321
F
Heating curve shift
0.0
-4.5
+4.5
ºC
1326
F
Heating curve adaptation
Off
Off On
1330
F
Winter/summer heating limit
18
---/8
30
ºC
1340
F
Min. drive limit
8
8
P 1.314
ºC
1341
F
Max. drive limit
80
P 1.340
80
ºC
9.7
Maintenance Parameters
Operation line
Operation
level
Feature
Default value
Min
Max
Unit
7044
F
Range of months for maintenance
12
---
12
Months
7170
F
SAT phone
0000xxxxxxxxx
-
-
Tel.
10
Alarm Codes
Biofell
boilers are equipped with an electronic circuit capable of detecting any malfunction through a continuous self-test. When the control panel detects a
malfunction, it signals it with the icon . If this happens, press the "Info" button to find out what triggered the alarm. The following list breaks down the main
alarm codes and their meanings:
Code
Description
Effect
0 No
error
10
Error in external probe
Disables affected part
20
Error in boiler 1’s temperature probe 1 (one-way probe) / Water pressure switch failure
Stops the entire system
30
Error in flow temperature probe 1 (CC1 probe)
Disables affected part
50
Error in DHW temperature sensor 1 (DHW thermostat/ probe)
Stops the entire system
60
Error in room temperature sensor 1 (CC1)
Disables affected part
68
Error in room temperature sensor 3 (CCP)
Disables affected part
81
LPB short circuit (RVS63 switchboard)
Disables affected part
83
BSB cable short circuit (room temperature sensor)
Disables affected part
84
BSB address collision (room temperature sensor)
Ignores affected part
85
BSB radio communications failure (room temperature sensor)
Disables affected part
105
Maintenance message
View maintenance code table
126
DHW load monitoring
Disables affected part
131
Burner failure. Error in safety thermostat
Stops the entire system
146
Common configuration error message
Ignores affected part
217
Common sensor error message
Disables affected part
326
BX/mixing valve group, same sensors
Ignores affected part