Biofell Cascade
601130040 [Revision 1502.00] [subject to changes with no previous notice]
Page 13 of 20
Operation
Display
Description
Configuration
Fault
LPB system
Turn the setting knob to access the “LPB system” menu.
Press OK.
LPB system
Device address
Press OK to enable value modification.
Turn the setting knob to modify the set value.
Press OK to confirm the new value.
Press ESC to return to the default display.
Each module’s address correspond to the number selected in this parameter:
Parameter
value
Module Parameter
value
Module Parameter
value
Module Parameter
value
Module
1
Module 1
5
Module 5
9
Module 9
13
Module 13
2
Module 2
6
Module 6
10
Module 10
15
Module 14
3
Module 3
7
Module 7
11
Module 11
15
Module 15
4
Module 4
8
Module 8
12
Module 12
16
Module 16
Repeat this procedure for all modules, sketching their place in the cascade.
The segment address in the 6601 parameter should be set to 0 for all modules. To this effect:
Operation
Display
Description
Boiler temp
Default display. If not shown, press the ESC button to return to it.
Press OK.
Time of day and date
Operator section
Hold the INFO button for 5 seconds.
Enduser
Commissioning
Commissioning
OEM
Engineer
Turn the setting knob to access the “Engineer” menu.
Press OK.