Page 16 of 20
601130040 [Revision 1502.00] [subject to changes with no previous notice]
Biofell Cascade
Operation
Example display
Description
Press OK.
Time of day and date
Operator section
Configuration
Fault
LPB system
Turn the setting knob to access the “LPB system” menu.
Press OK.
At this point we can access the system parameters by turning the setting knob.
9.1
Operation Levels
User:
E
Start-up:
I
Engineering:
F
OEM: Not accessible without a code
9.2
LPB Parameters
Operation line
Operation
level
Feature
Value to adjust
Min
Max
Unit
6600 F
Device
address
1
1
16
1
6601
F
Segment address
Always 0
0
0
0
9.3
Configuration Parameters
Operation line
Operation
level
Feature
Value to adjust
Min
Max
Unit
5730
F
DHW B3 probe
Probe
Thermostat
Probe
-
5731
F
DHW B3 actuator
Pump
Pump
V3V
-
5930
F
BX1 probe input
B10 common drive probe
-
-
-
5932
(Biofell Sun only)
F
BX3 probe input
B10 common drive probe
-
-
-
5960
F
H3 feature input
0-10V heat demand
5964
F
H3 10V temperature
50/80
8
85
ºC
9.4
Boiler Parameters
Operation line
Operation
level
Feature
Default value
Min
Max
Unit
2210
F
Primary’s min. temperature
8
8
Manual set
ºC
2212
F
Primary’s max. temperature
80
Manual set
85
ºC
9.5
DHW Parameters
Operation line
Operation
level
Feature
Value to adjust
Min
Max
Unit
1610
E-F
DHW B3 probe
Probe
Thermostat
Probe
-
1640
F
Anti-Legionella feature
Off, Periodically, Fixed day
Periodically
-
-
-
1641 F
Anti-Legionella feature period
7
1
7
Days
1642
F
Anti-Legionella feature fixed-day activation
Saturday
Monday
Sunday
-
1644 F Anti-Legionella feature activation time
03:00
00:00
23:50
hh:mm
1645
F
Anti-Legionella feature max. temperature setting
70
55
95
ºC
1646 F
Anti-Legionella feature max. activation interval
30
10
360
min
5020
F
Primary’s temperature increase on DHW
temperature set
12 (SUN/M models)
20 (T/BV/AS models)
0
30
ºC
9.6
CCP/CCB Heating Parameters
Operation line
Operation
level
Feature
Default value
Min
Max
Unit