Page 18 of 20
601130040 [Revision 1502.00] [subject to changes with no previous notice]
Biofell Cascade
11
Settings Tab
In order to facilitate subsequent interventions, the values set at commissioning should be recorded on the following table:
Manufacturing No.
Module No.
Manufacturing No.
Module No.
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
Configuration
Operation line
Operation
level
Feature
Value to set
Adjusted value
5730
F
DHW B3 probe
Probe
5731
F
DHW B3 actuator
Pump
5930
F
BX1 probe input
B10 common drive probe
5932 (
Biofell
SUN
only
)
F
BX3 probe input
B10 common drive probe
5960
F
H3 feature input
0-10V heat demand
5964
F
H3 10V temperature
50/80
Boiler
Operation line
Operation
level
Feature
Default value
Adjusted value
2212
F
Max. primary’s temperature
40/80
Domestic hot water
Operation line
Operation
level
Feature
Value to set
1610
E-F
DHW B3 probe
Probe/Thermostat
1640
F
Anti-Legionella feature
Off, Periodically, Fixed day
Off/Periodically/Fixed day
1641
F
Anti-Legionella feature period
7
1642
F
Anti-Legionella feature fixed-day activation
Saturday
1644
F
Anti-Legionella feature activation time
03:00
1645
F
Anti-Legionella feature max. temperature setting
70
1646
F
Anti-Legionella feature max. activation interval
30
5020
F
Primary’s temperature increase on DHW
temperature set
20
CCP/CCB heating
Operation line
Operation
level
Feature
Default value
1320
E-F
Heating curve slope
1.5
1321
F
Heating curve shift
-4,5ºC ÷ +4,5ºC
1326
F
Heating curve adaptation
Off/On
1330
F
Winter/summer heating limit
8ºC ÷ 30ºC
1340
F
Min. drive limit
8
1341
F
Max. drive limit
80
Maintenance
Operation line
Operation
level
Feature
Default value
7044 F
Range of months for maintenance
12
12
Monitoring and Maintenance Plan
Preventive maintenance requires performing the tasks listed below for their record keeping. Omission thereof may void the warranty.