Biofell Cascade
601130040 [Revision 1502.00] [subject to changes with no previous notice]
Page 15 of 20
Operation
Display
Description
Commissioning
OEM
Engineer
Turn the setting knob to access the “Engineer” menu.
Press OK.
Time of day and date
Operator section
DHW storage tank
LPB system
Configuration
Turn the setting knob to access the “Configuration” menu.
Press OK.
At this point we can access the configuration parameters by turning the setting knob. The parameters to be configured in module 1 are:
Parameter 5730: DHW probe or thermostat (thermostat incompatible with the Anti-Legionella feature)
Parameter 5731: Q3 DHW actuator - Charge pump/diverter valve
Parameter 5930: BX1 probe input - B10 common drive probe
Furthermore, if the cascade system comprises
Biofell SUN
, it must be set as follows:
Parameter 5932: BX3 probe input - B10 common drive probe
8
Temperature Display
The flow sensor/collector temperature is displayed in the control panel of the boiler set as module 1. The temperature displayed in other modules viewports
will be specific to each module.
9
System Parameters
To configure the system, one must access the "Engineering (
F
)" level, and proceed as follows:
Operation
Example display
Description
Boiler temp
Default display. If not shown, press the ESC button to return to it.
Press OK.
Time of day and date
Operator section
Hold the INFO button for 5 seconds.
Enduser
Commissioning
Turn the setting knob to access the “Engineer” menu.