TSC 80 TRANSFER SWITCH CONTROLLER
PM063 Rev 7 09/02/27
Thomson Technology
28
TABLE 1
USER ADJUSTABLE FEATURES
Function
Factory Default Setting
Range
Engine Start Timer
3 seconds
0-60 sec
Engine Warm-up Timer
2 seconds
0-60 sec
Engine Cooldown Timer
2 minutes
0-30 min
Utility Return Timer
2 minutes
0-30 min
Neutral Delay Timer
3 seconds
0-60 sec
Utility Under Voltage Sensor
(Drop-Out Setting)
85%
70-95%
Generator Under Voltage
Sensor (Drop-Out Setting)
85%
70-95%
Generator Frequency Sensor
90%
70-90%
4.2.1. UTILITY UNDER VOLTAGE SETPOINT
A potentiometer is provided to adjust the setpoint of the TSC 80’s utility under voltage
sensor. The under voltage setting is expressed in percentage of system voltage setting
with an adjustable range of 70-95% (e.g. If system voltage configuration jumper is set
for 600V, an 80% under voltage setting will correspond to an actual 540VAC setpoint.)
NOTE
The actual under voltage setpoint voltage is calculated based
on the TSC 80 voltage configuration jumper setting (i.e. nominal
system voltage) and the potentiometer setting. Actual system
operating voltage should not be used to calculate the under
voltage setpoint.
The under voltage setting is for a falling utility voltage (i.e. “drop-out” setting) on any
one phase. The under voltage sensor will reset to normal when the utility voltage rises
5% above the “drop-out setting (i.e. differential value). Example: if under voltage is
adjusted to an 80% drop-out value, it will reset at 85% voltage. The 5% differential
value is not programmable.