TSC 80 TRANSFER SWITCH CONTROLLER
PM063 Rev 7 09/02/27
Thomson Technology
10
2.2.3.
ADJUSTMENT POTENTIOMETERS
The TSC 80 controller utilizes eight adjustment potentiometers, which are mounted on
the printed circuit board as per FIGURE 2. They are used for adjustment of all time
delays, voltage and frequency setpoints. All potentiometers will be set to factory
default values. Refer to
Section 4.0 (CONFIGURATION INSTRUCTIONS)
for further
information.
2.2.4.
CONFIGURATION JUMPERS
The TSC 80 controller utilizes eight Configuration Jumpers, which are mounted on the
printed circuit board as per FIGURE 2. They are used for configuration of main system
operating parameters such as voltage, frequency and phases. Refer to
Section 4.0
(CONFIGURATION INSTRUCTIONS
) for further information.
2.3.
TSC 80 CONTROLLER FEATURES
The Thomson Technology TSC 80 Transfer Switch Controller utilizes the latest advancements
in microprocessor technology, printed circuit board assembly and software for control of
automatic transfer switches. The TSC 80 is the second generation of microprocessor-based
transfer switch controllers from Thomson Technology, and reflects over 30 years of transfer
switch control experience. The TSC 80
is factory configured to monitor, display and control all
operational functions of the automatic transfer switch. All voltage sensors and timers are fully
user adjustable utilizing potentiometers, which requires no software configuration. The
microprocessor design provides high accuracy for all voltage sensing and timing functions as
well as providing many standard features.
•
Utility AC voltage sensing (true RMS) – 120-600V single phase or 3 phase
•
Generator AC voltage sensing (true RMS) – 120-600V single phase or 3 phase
•
Generator AC frequency sensing
•
Utility under voltage control setpoint 70 - 95% (adjustable)
•
Generator under voltage control setpoint 70 - 95% (adjustable)
•
Generator under frequency control setpoint 70 - 90% (adjustable)
•
Engine warm-up timer 0-60 sec. (adjustable)
•
Utility return timer 0-30 min. (adjustable)
Summary of Contents for TSC 80