TSC 80 TRANSFER SWITCH CONTROLLER
PM063 Rev 7 09/02/27
Thomson Technology
21
NOTE
The Lamp Test Function will also clear a transfer failure alarm
and will allow active timers to be bypassed if the lamp test is
held on for longer than 5 seconds.
3.5.
TIMER BYPASS
To bypass an active timing sequence (e.g. utility return timer, cooldown timer, warm-up
timer) during operation, both Lexan faceplate pushbuttons (i.e. UTILITY POWER FAIL
SIMULATE & GENERATOR EXERCISE MODE) must be held on for approximately 5
seconds until all LEDs on the Lexan start flashing and UTILITY POWER FAIL
SIMULATE LED flashes in opposition.