TSC 80 TRANSFER SWITCH CONTROLLER
PM063 Rev 7 09/02/27
Thomson Technology
24
4.1.1.1.TSC 80 UNDER VOLTAGE SETPOINTS WITH NON-STANDARD
SYSTEM VOLTAGES
When the Transfer Switch & TSC 80 transfer controller is applied to non-
standard system voltages, the TSC 80 under voltage potentiometer setting
percentages on the printed circuit board will not correspond to the correct
voltage drop out setting.
To obtain the correct drop-out voltages using non-standard system voltages,
the TSC 80 potentiometers need to have an offset percentage adjustment with
the corresponding Voltage Jumper settings. These are shown in the following
table for typical 85% drop-out under voltage setpoints.
System
Voltage
ATS
Transformer
Tap Setting
TSC 80 Voltage
Jumper Setting
85% Drop-out
Voltage
TSC 80 Under
voltage
Potentiometer
Setting
208V
208V tap
No jumper =
208V
177V
85%
220V
240V tap
240V
187V
78%
230V
240V tap
240V
195V
81%
240V
240V tap
240V
204V
85%
440V
480V tap
480V
374V
78%
460V
480V tap
480V
391V
81%
480V
480V tap
480V
408V
85%
575V
600V tap
600V
489V
82%
380V/50Hz
392V tap (use
208V to 600V
primary
connection)
380V
323V
85%
400V/50Hz
392V tap (use
208V to 600V
primary
connection)
480V
340V
71%
To obtain the most accurate setting of the potentiometer (other than visually on the
printed circuit board), a Service Display Module (SDM) is recommended.
For other non-standard system voltages, the following formula can be used:
A) Desired Drop-out Voltage= Drop-out % x System Voltage