Timer (delay): The timer setting is the time that must expire from the alarm level is reached until
the alarm occurs.
Relay output A: A relay can be activated by output A.
Relay output B: A relay can be activated by output B.
Enable:
The alarm can be activated or deactivated. ON means always activated.
Inhibits:
It is possible to inhibit some of the alarms. This means it is only activated when the
running feedback signal is present.
Inhibit functions:
Fail class:
When the alarm occurs, the unit will react depending on the selected fail class.
Fail class
The fail class settings for the protections have the following possibilities:
Value
Comment
0: Warning
Shown in alarm pop-up window and activates the chosen
relays.
1: Trip
Shown in alarm pop-up window and activates the chosen
relays. Trips the breaker.
2: Trip and stop
Shown in alarm pop-up window and activates the chosen
relays. Trips the breaker, cools down the engine and
stops it.
3: Shutdown
Shown in alarm pop-up window and activates the chosen
relays. Trips the breaker and shuts the engine down
immediately.
Small differences due to the character of the parameters may exist between the
individual tables.