MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 48
THOMSON TECHNOLOGY
Counters
Counters for various values are included, and some of these can be adjusted if necessary, for
instance if the unit is installed on an existing gen-set or a new circuit breaker has been installed.
The table shows the adjustable values and their function in menu 6100: Description Function
Comment.
Description
Function
Comment
6101 Running time
Offset adjustment of the total running
hours counter.
Counting when the running
feedback is present.
6103 GB operations
Offset adjustment of the number of
generator breaker operations.
Counting at each GB close
command.
6105 kWh reset
Resets the kWh counter.
Automatically resets to OFF
after the reset. The reset
function cannot be left active.
Command timer
The purpose of command timer is to be able to start and stop the gen-set automatically at specific
times each weekday or certain weekdays. Up to 8 commands can be used for either start or stop.
The settings are set up through the TPS 300 software. Each command can be set for the following
time periods:
•
Individual days (MO, TU, WE, TH, FR, SA, SU)
•
MO, TU, WE, TH
•
MO, TU, WE, TH, FR
•
MO, TU, WE, TH, FR, SA, SU
•
SA, SU
Select command timer function
Select day(s) command timer should be active
The service timer alarm must be reset in the parameter list via the MEC 310 display
or via the utility software in parameter 6116 or 6126 to remove the actual alarm.