MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 93
THOMSON TECHNOLOGY
1250 Gen underfrequency 2
No.
Setting
Min. setting
Max. setting
Third
setting
Factory
setting
1251
Underfrequency 2 (P2) Set point
50.0%
110.0%
-
85.0%
1252
Underfrequency 2 (P2) Timer
0.1 s
100.0 s
-
5.0 s
1253
Underfrequency 2
Relay output
A
R0 (none)
R26 (relay 26) -
R0 (none)
1254
Underfrequency 2
Relay output
B
R0 (none)
R26 (relay 26) -
R0 (none)
1255
Underfrequency 2
Enable
OFF
ON
Inhibits
ON
1256
Underfrequency 2
Fail class
Warning
Shutdown
-
Warning
1450 Gen overload 1
No.
Setting
Min. setting
Max. setting
Third
setting
Factory
setting
1451
Overload 1(P2)
Set point
10.0%
200.0%
-
100.0%
1452
Overload 1(P2)
Timer
0.1 s
3200.0 s
-
5.0 s
1453
Overload 1
Relay output A R0 (none)
R26 (relay 26) -
R0 (none)
1454
Overload 1
Relay output B R0 (none)
R26 (relay 26) -
R0 (none)
1455
Overload 1
Enable
OFF
ON
Inhibits
ON
1456
Overload 1
Fail class
Warning
Shutdown
-
Warning
1460 Gen overload 2
No.
Setting
Min. setting
Max. setting
Third
setting
Factory
setting
1461
Overload 2(P2)
Set point
10.0%
200.0%
-
110.0%
1462
Overload 2(P2)
Timer
0.1 s
3200.0 s
-
5.0 s
1463
Overload 2
Relay output A R0 (none)
R26 (relay 26) -
R0 (none)
1464
Overload 2
Relay output B R0 (none)
R26 (relay 26) -
R0 (none)
1465
Overload 2
Enable
OFF
ON
Inhibits
ON
1466
Overload 2
Fail class
Warning
Shutdown
-
Warning
2150 Phase sequence error
No.
Setting
Min. setting
Max. setting
Third
setting
Factory
setting
2152
Phase seq error
Timer
0.0 s
10.0 s
-
1.0 s
2153
Phase seq error
Relay output A R0 (none)
R26 (relay 26) -
R0 (none)
2154
Phase seq error
Relay output B R0 (none)
R26 (relay 26) -
R0 (none)
2155
Phase seq error
Enable
OFF
ON
Inhibit
OFF
2156
Phase seq error
Fail class
Warning
Shutdown
-
Warning
2160 GB open failure
No.
Setting
Min. setting
Max. setting
Factory
setting
2161
GB open failure
Timer
0.0 s
10.0 s
1.0 s
2170 GB close failure
No.
Setting
Min. setting
Max. setting
Factory
setting
2171
GB close failure
Timer
0.0 s
10.0 s
1.0 s