MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 94
THOMSON TECHNOLOGY
2280 Phase rotation
No.
Setting
Min. setting
Max. setting
Factory
setting
2281
Phase rotation
Setpoint
L1L2L3
L1L3L2
L1L2L3
2282
Phase rotation
Password
Customer
Service
Customer
2770 EIC control
3000-3050 Digital input term. 10-15, without wire break
No.
Setting
Min. setting
Max. setting
Third
setting
Factory
setting
30X1
Dig. input no. XX
Timer
0.0 s
3200.0 s
-
10.0 s
30X2
Dig. input no. XX
Relay output A
R0 (none)
R26 (relay 26) -
R0 (none)
30X3
Dig. input no. XX
Relay output B
R0 (none)
R26 (relay 26) -
R0 (none)
30X4
Dig. input no. XX
Enable
OFF
ON
Inhibit
OFF
30X5
Dig. input no. XX
Fail class
See description of fail classes
30X6
Dig. input no. XX
NO/NC
NO
NC
-
NO
3490 Emergency stop (terminal 19-20)
No.
Setting
Min. setting
Max. setting
Factory
setting
3491
Emergency STOP
Timer
0.0 s
60.0 s
0.2 s
3492
Emergency STOP
Relay output A
R0 (none)
R26 (relay 26)
R0 (none)
3493
Emergency STOP
Relay output B
R0 (none)
R26 (relay 26)
R0 (none)
3494
Emergency STOP
Enable
OFF
ON
ON
3495
Emergency STOP
Fail class
See description of fail classes
No.
Setting
Min. setting
Max. setting
Factory setting
2771
EIC Control
Droop
0.0%
25.0%
0.0%
2772
EIC Control
Scania rpm
User
1500 rpm
1800 rpm
Low idle
User
2773
EIC Control
Cummins gain
0.00
10.00
5.00
The setting of Phase rotation depends of the wiring of Mains L1, L2 and L3.