11.3.2 Commands (Holding Register)
All commands of the wind transmitter occupy 32bit, i.e. 2 MODBUS register addresses and
represent unsigned integers. The following example shows the change of the baud rate to
19200 baud.
1. Set password for the user level (KY=234)
Slave
address
Functional
code
Start
address
Number
register
Number
byte(s)
Data
CRC
0x01
0x10
0x9C 49 0x00 02
0x04
0x00 00 00 EA 0x4F 7C
CRC
low-byte
CRC
high-byte
2. Set command baud rate to 19200 baud (BR=6)
Slave
address
Functional
code
Start
address
Number
register
Number
byte(s)
Data
CRC
0x01
0x10
0x9C 45 0x00 02
0x04
0x00 00 00 06
0x4E A4
CRC
low-byte
CRC
high-byte
The commands available for parameter setting are listed in the chapter 9.2 commands and
description.
11.3.3 Calibration Tables in the MODBUS-RTU Interpreter
The following table shows the registers available for reading out the calibration table:
Regis-
ter-ad-
dress
Parameter Name
Value range
Meaning
File
type
Authoriza-
tion type
41000
…
41075
standard characteristic
152 Bytes
Read standard char-
acteristic
Read
41076
…
41151
Newest Calibration table
152 Byte(s)
Read calibration data
Read
41152
…
41227
2. Newest Calibration table
152 Byte(s)
Read calibration data
Read
41228
…
41303
3. Newest Calibration table
152 Byte(s)
Read calibration data
Read
41304
…
41379
4. Newest Calibration table
152 Byte(s)
Read calibration data
Read
41380
…
41455
5. Newest Calibration table
152 Byte(s)
Read calibration data
Read