BOILER MOUNTING
INSTALLATION
9
3.3.
Chimney
The chimney installation must supply sufficient draught, air tightness and protection against
condensation.
The appropriate chimney installation is very important for the boiler’s efficient
and safe function!
The chimney must be positioned if possible in the interior of the building. It must be vertical,
with no changes in the direction. The cross-section of the chimney can be round or rectangular.
If the chimney is installed in the exterior, it must be insulated.
The horizontal part connecting the boiler’s chimney pipe with the vertical chimney must have
maximum length 2 m. If this distance is bigger, it is recommended to have a 15-30
o
inclination
upwards. The connection with the boiler’s chimney pipe must be air-tight.
The chimney must be equipped with a cleaning door at its base. Also cleaning doors are
recommended where there are changes in direction and ash can be accumulated. Tactical
cleaning is recommended (every 3 months) for efficient boiler function.
A chimney terminal must be installed at the end of the chimney for protection against weather
effects and foreign objects entrance. In areas with strong winds a special anti-downdraught
terminal is recommended.
The chimney height must exceed the roofline by at least 1 m. If there are other obstacles
positioned on the roof, the chimney height must exceed them by at least 1 m. If there are
multiple chimneys, minimum distance between them is 0,3m.
Each boiler should be connected to an independent chimney. Connection of multiple boilers to
the same chimney is not recommended.
Fig 3.
Chimney distances
Fig 4.
Chimney connection