TECHNICAL FEATURES AND DIMENSIONS
5
2.3.
Dimensions
*Nominal output is obtained with premium quality wood pellet, DIN+ certification.
TYPE
W
W1
B
C
H
L
T1-T2
T3
T5
T6
mm
mm
mm
mm
mm
mm
inch
mm
inch
inch
PLC 25
670
1270
820
550
1500 1100
1 ½”
139
½”
½”
PLC 35
670
1270
820
650
1500 1200
1 ½”
139
½”
½”
PLC 50
750
1350
970
850
1500 1260
2”
159
½”
¾”
PLC 80
855
1455 1055 1050 1500 1550
2”
193
½”
1”
TECHNICAL DATA
Boiler
type
Nominal
Output*
T
max
P
max
Effici
ency
Water
contents
Electrical
connections
Weight
kW
o
C
bar
%
lit
V/Hz
kg
PLC 25
25
90
3
91,5
80
230/50
200
PLC 35
35
90
3
91,5
100
230/50
220
PLC 50
50
90
3
91,5
120
230/50
280
PLC 80
80
90
3
91,5
140
230/50
310