INSTALLATION
9
3.
BOILER MOUNTING
3.1.
Transportation and delivery
The boiler is delivered on wood pallet, well positioned with metal plates. Remove them carefully
by unscrewing the screws holding them in place.
The loading and unloading of the boiler must be performed with a forklift or a crane.
The boiler is very heavy. Do not try to lift by hands or other unsuitable
equipment. Danger of injury! Perform all moves with extreme caution.
Remove the boiler packaging with attention. Keep the packaging material away from
children since it can be dangerous. After having unpacked everything, make sure that the
appliance is intact and undamaged. In case of doubt do not use the appliance and inform the
supplier.
The ECOTWIN boiler is delivered with the following equipment:
Boiler steel body
Rockwool insulation mounted on the boiler body
Metal covers mounted on the boiler body
Pellet burner
Fuel feeder
Fuel tank
Ash box
Cleaning tools
Chain regulator
A second door for alternative wood combustion (optional)
In the documentation folder you will find:
Technical manual
Warranty leaflet
Declaration of conformity
3.2.
Boiler room
3.2.1.
General requirements
The boiler must be installed in a special and separate room. This room must be chosen so that
it offers easy access for fuel transport, air supply and exhaust gas evacuation. The doors of the
boiler room must be metallic, open outwards, and have at least 0,9 m width.
The boiler installation is prohibited in rooms with extensive dust, dangerous
gases, and moist spaces.
For the correct boiler function it is necessary that the boiler room has openings for natural
ventilation and combustion air supply. It is recommended that two different openings are used
for this purpose, positioned on opposite walls and diagonally to ensure good air circulation. The
total surface of the openings must be at least 1/12 of the boiler room surface. Forced ventilation
is prohibited in the boiler room.
The boiler room must be provided with a drainage channel. All safety devices must be connected
to this channel.
The boiler room must have an appropriate fire extinguishing system, according to the regulations
in force. In case that the building is designed with a fire alarm system, a smoke detector must
be positioned on top of every boiler.
The fuel storage is prohibited in the boiler room. If so, the storage must be separated from the
boiler with a non-flammable wall, and proper distanced from the boiler.