SERVICE AND MAINTENANCE
29
Check the fan and make sure it functions properly. Clean from dust and check that the air
passage is clear of obstacles and dust.
Remove the turbinators from the heat exchanger and check their condition.
It is recommended that you clean the chimney box of the boiler and the chimney pipes at least
every 3-4 months, in order to assure efficient and safe function of the boiler.
8.5.
Basic service procedures
8.5.1.
Service after overheating
If overheating occurs, the safety valves of the boiler must open.
Make sure the boiler pump is working. In case of blackout open all the valves of the system to
let hot water out of the boiler. In any case a blackout protection UPS is recommended to be
installed on the boiler pump.
If the chimney damper is not fully opened, put it in fully open position.
All safety devices must lead to drainage! After overheating, make sure that all the water from
the safety devices has drained, and the system has filled with cold water. Check the pressure
and the temperature of the boiler.
At overheating, the safety thermostat will activate, and cut electrical supply to the fan. In that
case, you need to manually reset the safety thermostat and put the system back in function.
Unscrew the plastic cover of the safety thermostat and press the switch. Put the plastic cover
back.
Verify the causes of the overheating! If it happens again, check the installation
and function of the pumps and safety devices!
8.5.2.
Restart the burner after an error
1. Turn off the burner by using the electric switch the burner is connected.
2. Open the boiler's door and check the burner tube.
3. Remove any ashes and impurities from burner fire chamber.
4. Close the door and switch on the controller by using the electric switch the burner
is connected
5. By pressing the button “MODE/ “ once changes the operation from “Stop” to “ignition”.
By pressing the button “MODE/ “ changes the operation from “Ignition” to “Automatic"
8.6.
Maintenance after long stop
It is necessary to perform a general maintenance and cleaning of the boiler after the heating
season. Clean thoroughly all the surfaces of the boiler as described in the corresponding
paragraph. Also clean the chimney box, and all the chimney parts where ash might be deposited.
After cleaning all the ash, empty the ash box and leave the boiler clean for the next winter
season.
After long stop of the boiler, before you put in function you need to perform the following checks:
Check the condition of the electric cables and the sensors. Make sure they are not damaged.
Check that the thermometer indicates the correct temperature and all the thermostats
function properly. Make sure the bulbs are properly positioned in the case.
Make a general check of the chimney and make sure it is clean and free of obstacles.
Verify the pressure in the heating network and the boiler.
Do not empty the water of the boiler and the heating installation after the heating
season! It will corrupt all the installation and especially the boiler.