BOILER START-UP
25
7.7.
Operation mode
7.7.1.
Starting the burner
1.
Activate the burner by connecting it with a power supply (230Volt, 50Hz)
2.
It is written on the LCD screen the following
3.
By pressing the button “MODE/ “ once changes the operation from “Stop” to “ignition”.
By pressing the button “MODE/ “ changes the operation from “Ignition” to “Automatic”.
4.
In “Automatic mode”, starts the operation of the burner.
5.
When the photo sensors detects fire, then the burner starts its “Work” by increasing its power
gradually to the power it has been set (i.e 30kW)
6.
When the boiler's water temperature reaches the desired temperature “HEATING WATER
TEMPERATURE “, the the power of the burner goes down ta 3kW (Maintain mode)
7.
The burner works at “Maintain mode” till the boiler's water temperature goes down to the
temperature:
“HEATING WATER TEMPERATURE - CH FURNACE HYSTERESIS”
7.7.2.
Stopping the burner
1. The burner can be either at “Work” or “Maintain” or “standby”
2. Press the button “MODE/ “continuously till “STOP MODE” appears on the screen.
3. It is written “Burning off” till the photo sensor stops to detect fire (3-5 min)
4. When the photo sensor stops to detect fire, “cleaning procedure takes place for few seconds.
7.7.3.
Changing from pellet to wood
The boiler does not change automatically from one fuel to the other. It is prohibited to use
wood when the burner is installed on the boiler. When using wood, remove the burner
according to the instructions below:
1.
Stop the burner function according to paragraph 7.7.2.
2.
Wait for the burner to completely burn-off the pellets and enter in stop mode.