BOILER START-UP
24
Do not load fuel manually directly to the burner! The pellet loading must only be
performed through the pellet feeder!
7.5.
Feeder filling procedure
1.
Remove the plastic tube connection the burner with the feeder
2.
Burner must be at stop mode. So, “Stop” appears on the LCD scree
3.
By pressing the button “MODE/ “ once changes the operation from “Stop” to “ignition”.
4.
“CHOICE FUNCTION-/+” appears on the LCD screen
5.
Press the button to start the feeder
6.
Feeders operation lasts 11min (Manufacturer's setting / Feeder's filling time"
7.
When the wood-pellet starts to come out of the feeder, press to stop the feeder
8.
Connect the feeder with the burner, by using the plastic pipe.
9.
If the "Feeder's filling time" is not enough, press to start the feeder again
7.6.
Checks to carry after initial start-up
During the first start-up you need to carefully check the air-tightness of all the connections,
especially the doors and the connection with the chimney.
Check that the thermostats function properly and devices operate accordingly. Wait for the boiler
to reach the preset temperature and make sure the fan stops properly and the flame falls down.
Check the temperature and pressure rise in the network. Make sure it is according to the
indications. Check if there is any water leakage in the network.
After burning of the fuel is completed, check the situation inside the boiler. If the walls are too
black, it means that there is insufficient air supply. If there is condensation forming on the boiler
walls, it means that the pump operation starts at a low temperature or the fuel has too big
humidity content. Make sure you set the pump according to the indications and you install a
return temperature protection system as indicated.