4001150-6
Page 5 of 128
Safety and Electrical Connections
All electrical wiring and connections MUST be carried out by a competent qualified
electrician in accordance with the latest edition of the IEE wiring regulations and/or
local statutory regulations.
A single phase or 3 phase isolator with a contact separation of at least 3mm in all poles
must be fitted to the supply wiring (the isolator must be fitted in an accessible position).
The air curtain must be earthed.
The appliance must be connected using cables having an appropriate temperature
rating (heat resistant).
Ensure that the supply cables, circuit breakers and other electrical installation
equipment are correctly sized for the air curtain being installed; see Table 2.
On a 3 phase electrical supply the unit requires a neutral connection (3N~).
Cable glands used for the Electrical Input must be rated IP21 or higher.
Table 2
Air Curtain
Electrical
Supply
(V/ph/Hz)
Rated Power
Input (kW)
Current per
phase (A)
Heat Output
(kW)
Weight
(kg)
C1000AR 230/1/50
0.15
0.7
N/A
19
C1500AR 230/1/50
0.20 0.9 N/A 25
C2000AR 230/1/50
0.25 1.1 N/A 35
C1000WR 230/1/50
0.15 0.7 6.0 20
C1500WR 230/1/50
0.20 0.9 9.0 27
C2000WR 230/1/50
0.25 1.1 12.0 37
C1000ER 400/3/50
9.15
13.7 4.5/9.0 22
C1500ER 400/3/50
12.20 18.3
6.0/12.0 30
C2000ER 400/3/50
18.25 27.2
9.0/18.0 41
Fitting/Connecting the Ecopower Remote Control (excluding Ambient)
The remote control unit should be located in
a suitable place for easy access, it can be
fixed to the wall via two key-hole slots. Drill
and fix the screws into the wall leaving a
small gap between the head and the wall,
lower the unit onto the screws, for fixing
centres see adjacent figure. Ensure
suitable fixing screws are used.
The remote control is supplied with 3m of cable and a pre-fitted RJ connecting plug.
Ensure the remote control cable is safely secured and connected.
80mm
3.5mm
6mm