LPHW Models
For LPHW models ensure suitable water mains isolation valves are fitted in the flow
and return pipework.
When fitting the 3-port valve ensure that the pipe connections are fitted as detailed
below and are in accordance with the manufacturers leaflet supplied with the valve.
Air Curtain
Water Flow Rate (l/s)
82/72 °C
Coil Water Pressure Drop (kPa)
C1000WR 0.14
2.77
C1500WR 0.21
6.74
C2000WR 0.29
13.40
Ambient Models
Ambient units are supplied with a remote switch
unit. The switch unit allows the air curtain to be
powered ON/OFF and select one of three fan
speeds.
Multiple Installation (Ecopower only)
To Master/Slave two or more air curtains together the remote control is plugged into
the Master unit and a RJ lead should be connected from the Master to the Slave
unit(s). Thermoscreens 3m RJ extension leads are available and must be ordered
separately. Additional air curtains, up to a maximum of eight units, may be connected
as indicated below. For Master/Slave configuration an independent mains supply as
per Table 2 must be supplied to each air curtain.