background image

 

4001150-6 

 

Page 7 of 128 

 

 

 

 LPHW Models 

 

For LPHW models ensure suitable water mains isolation valves are fitted in the flow 
and return pipework. 

 

When fitting the 3-port valve ensure that the pipe connections are fitted as detailed 
below and are in accordance with the manufacturers leaflet supplied with the valve. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Air Curtain 

Water Flow Rate (l/s) 

82/72 °C 

Coil Water Pressure Drop (kPa) 

C1000WR 0.14 

2.77 

C1500WR 0.21 

6.74 

C2000WR 0.29 

13.40 

 
 

 Ambient Models 

 

Ambient units are supplied with a remote switch 
unit. The switch unit allows the air curtain to be 
powered ON/OFF and select one of three fan 
speeds. 

 
 

 Multiple Installation (Ecopower only) 

 

To Master/Slave two or more air curtains together the remote control is plugged into 
the Master unit and a RJ lead should be connected from the Master to the Slave 
unit(s).  Thermoscreens 3m RJ extension leads are available and must be ordered 
separately.  Additional air curtains, up to a maximum of eight units, may be connected 
as indicated below.  For Master/Slave configuration an independent mains supply as 
per Table 2 must be supplied to each air curtain. 

 

 
 
 
 
 
 
 
 

 

 

Summary of Contents for C1000AR

Page 1: ...4001150 6 Page 1 of 128 C RECESSED RANGE AIR CURTAINS INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION ...

Page 2: ...ote Control Ecopower Electric LPHW Manual Ambient Recessed Grille If anything is missing or damaged please contact your place of purchase immediately For your records Date of Purchase Place of Purchase Serial Number For warranty purposes proof of purchase is necessary so please keep a copy of your invoice All documentation supplied with each unit should be stored and kept for future reference ...

Page 3: ...ll need an air ventilation grille of effective free area cm2 as given in Table 1 and an adequate air path within the void for air to enter the punched air ventilation slots Table 1 Air curtain Required air flow within ceiling void m3 hr Effective free area of ventilation grille for an enclosed ceiling void cm2 C1000R 353 500 C1500R 421 700 C2000R 707 1200 Ceiling Suspension Make the cut out in the...

Page 4: ...29 A mm 1529 C2000R 2040 2090 1209 1609 2120 C 353 CEILING LEVEL 257 B 206 Electrical supply inlet 22 A 301 33 165 1m 140 1 5m 140 2m 150 Figure 1 Length mm Width mm Cut Out in Ceiling 1579 1179 2090 311 311 311 LPHW connections Rp 1 2 1 2 BSP female 22 25 85mm ...

Page 5: ...Electrical Input must be rated IP21 or higher Table 2 Air Curtain Electrical Supply V ph Hz Rated Power Input kW Current per phase A Heat Output kW Weight kg C1000AR 230 1 50 0 15 0 7 N A 19 C1500AR 230 1 50 0 20 0 9 N A 25 C2000AR 230 1 50 0 25 1 1 N A 35 C1000WR 230 1 50 0 15 0 7 6 0 20 C1500WR 230 1 50 0 20 0 9 9 0 27 C2000WR 230 1 50 0 25 1 1 12 0 37 C1000ER 400 3 50 9 15 13 7 4 5 9 0 22 C1500...

Page 6: ...crew each M6 bolt through the slot in the grille bracket until all four are located into place Adjust the height of the grille frame via slots in brackets so the frame fits nicely against the under side of the ceiling Once the desired height is achieved tighten each M6 bolt in place locking the grille frame into the correct position Adjusting the Separator Plate Within the air curtain there is a s...

Page 7: ...odels Ambient units are supplied with a remote switch unit The switch unit allows the air curtain to be powered ON OFF and select one of three fan speeds Multiple Installation Ecopower only To Master Slave two or more air curtains together the remote control is plugged into the Master unit and a RJ lead should be connected from the Master to the Slave unit s Thermoscreens 3m RJ extension leads are...

Page 8: ...nsor thermistor on all units to be measuring DIP3 OFF Overheat Fan Disable If DIP4 is on and thermal overheat trips heat and fan circuits are isolated and LED s on wall switch flash If DIP4 is off and TOC trips out only the heat circuit is isolated and the LED s on the wall switch flash DIP4 Option Electric only Wall switch upgrade required The handset has to be powered on Independently set up DIP...

Page 9: ... contact the unit will run If it is open circuit across the terminal the unit will switch off This remote On Off feature has global switching logic i e if you master slave several units together you need connect the remote contact to only one of them to turn all units on and off in the master slave system As supplied a wire link will be fitted to the terminal block on every unit For summer setting...

Page 10: ...4001150 6 Page 10 of 128 ...

Page 11: ...4001150 6 Page 11 of 128 ...

Page 12: ...4001150 6 Page 12 of 128 ...

Page 13: ...r LED shows which fan speed is selected In Auto Mode the air curtain measures the incoming air temperature and automatically selects the necessary amount of heat to keep it at the level selected Heating level indicator LED s go from 0 to 100 in 8 steps to show the level selected In Manual Mode heat output can be selected as Zero Half Heat or Full Heat Heating level indicator LED s go 0 50 or 100 t...

Page 14: ...ault with electrical heated air curtains the thermal cut out s may operate Note If the mains supply is isolated during operation then the thermal cut outs may operate The thermal cut out s are located within the unit directly above the electric element banks one on the 1 1 5m and two on the 2m model There are two fuses on the Ecopower circuit board which may blow in the event of a fault For Ambien...

Page 15: ...ct Installer Service Agent to investigate why thermal cut out s have operated Service Agent to reset thermal cut out s Contact Installer Yes No Yes Yes No No No Yes Yes No No Is Electrical Power switched on Are the fans operating correctly Is the unit discharging warm air Check if thermal cut out s have tripped Electric Heated only Do the LED s light up on the remote control Is the remote control ...

Page 16: ...clean the build up of dirt and debris within the air curtain please note that the motor s are permanently lubricated and require no additional lubrication Once the air curtain has been cleaned check all electrical connections within the unit ensuring terminals are tight and that crimped connections have not become loose Re install the recessed grille ensuring the straight louvers are directly unde...