  Ecopower Controller Motherboard (v8) 

 
 

 

Function 

 

 

Control 

 

Comments 

 

Standard 

Fan Heat Interlock – 

The heat output is dependent on the fan 

speed. If low or medium fan speed is 
selected the heat output can only go up to 

first heat stage. Only if the unit is operating 

on high fan speed can the second heat 

stage be selected. This feature operates in 
manual or auto mode.  

DIP1 Option 

 

Suitable on vertical electrically heated 

Designer air curtain. Maximum heat 

output achieved if maximum fan speed 
selected.   Independently set-up DIP 

switch on each mother board. 

As supplied, the 

default setting would 

be for heat and fan 
settings to be 

independent (DIP1 

OFF). 

Disable Fan Run-on –  

Disable fan run-on. 

DIP2 Option  

(LPHW & 
Ambient only) 

 
 
 

Must only be used for LPHW and 

Ambient air curtains.  Independently set-

up DIP switch on each mother board. 

As supplied, the 

default setting would 

enable fan run-on 
(DIP2 OFF). 

Thermostat Master –  

Only the air sensor thermistor in the master 
air curtain will be used for measuring the 

reference air temperature for the whole 

master/slave installation.  

 

DIP3 Option  
 

The air sensor thermistors in all the slave 

air curtains will be ignored. This will then 

avoid situations on larger doorways with 
master/slave air curtains where some 

units can blow cold air whilst others can 

blow warm air, because they currently all 

refer to their own air sensor for control of 
the heat output of each air curtain.  

The master air curtain need not be the 

one that the wall control is plugged into.

 

As supplied, the 

default setting would 

be for the air sensor 
thermistor on all units 

to be measuring  

(DIP3 OFF). 

 

Overheat Fan Disable –  

If DIP4 is on and thermal overheat trips, 

heat and fan circuits are isolated and LED’s 

on wall switch flash.  If DIP4 is off and TOC 

trips out, only the heat circuit is isolated and 
the LED’s on the wall switch flash. 

DIP4 Option 

(Electric only

 

 

Wall switch upgrade required. 
The handset has to be powered on. 

Independently set-up DIP switch on each 

mother board. 

 
To remove fault, isolate electrical supply 

to air curtain, reset TOC and reconnect 

supply.

  

As supplied, the 
default setting would 

enable fan if TOC trips 

(DIP4 OFF). 

NB: If TOC operates 
with an upgraded 

switch the LED’s on 

switch flash, 

regardless of DIP4 
settings.

  

Retain User Settings (toggle) –  

If electrical supply to the air curtain is 

removed, upon restoring electrical supply 
the customer’s settings on the remote 

control will be retained, i.e. if unit were 

operating beforehand, it would 

automatically start up again and operate on 
the exact same settings as before.  

Optional 

feature –via 

secret key 
press (Fan-

down) 

Wall switch upgrade required. 

To toggle – switch unit on from handset.  

Hold Auto button till Auto LED flashes.  
Press fan down button to toggle 

selection. 

As supplied, the 

default setting would 

be for the unit to start 
up again automatically. 

Need to do the secret 

key presses to revert 

back to “nothing 

happens” when power 
is restored, as we have 

it now. 

Fan run-on time set two minutes. 

Built-in 

If “FAN ONLY” has been selected, at 

switch off, no fan run-on. 

 

Reduce time for fan speeds to turn on and 

index up through Low, Medium and High 

fan speed when turning on via the 

BMS/Remote On/Off option. 

Built-in  

 

 

              - white rectangle indicates the moveable head of each 4 way DIP switch 

ON 

OFF 

 1    2     3    4

ON 

OFF 

 1    2     3    4

ON 

OFF 

 1    2     3    4

ON 

OFF 

 1    2     3    4

Summary of Contents for C1000AR

Page 1: ...4001150 6 Page 1 of 128 C RECESSED RANGE AIR CURTAINS INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION ...

Page 2: ...ote Control Ecopower Electric LPHW Manual Ambient Recessed Grille If anything is missing or damaged please contact your place of purchase immediately For your records Date of Purchase Place of Purchase Serial Number For warranty purposes proof of purchase is necessary so please keep a copy of your invoice All documentation supplied with each unit should be stored and kept for future reference ...

Page 3: ...ll need an air ventilation grille of effective free area cm2 as given in Table 1 and an adequate air path within the void for air to enter the punched air ventilation slots Table 1 Air curtain Required air flow within ceiling void m3 hr Effective free area of ventilation grille for an enclosed ceiling void cm2 C1000R 353 500 C1500R 421 700 C2000R 707 1200 Ceiling Suspension Make the cut out in the...

Page 4: ...29 A mm 1529 C2000R 2040 2090 1209 1609 2120 C 353 CEILING LEVEL 257 B 206 Electrical supply inlet 22 A 301 33 165 1m 140 1 5m 140 2m 150 Figure 1 Length mm Width mm Cut Out in Ceiling 1579 1179 2090 311 311 311 LPHW connections Rp 1 2 1 2 BSP female 22 25 85mm ...

Page 5: ...Electrical Input must be rated IP21 or higher Table 2 Air Curtain Electrical Supply V ph Hz Rated Power Input kW Current per phase A Heat Output kW Weight kg C1000AR 230 1 50 0 15 0 7 N A 19 C1500AR 230 1 50 0 20 0 9 N A 25 C2000AR 230 1 50 0 25 1 1 N A 35 C1000WR 230 1 50 0 15 0 7 6 0 20 C1500WR 230 1 50 0 20 0 9 9 0 27 C2000WR 230 1 50 0 25 1 1 12 0 37 C1000ER 400 3 50 9 15 13 7 4 5 9 0 22 C1500...

Page 6: ...crew each M6 bolt through the slot in the grille bracket until all four are located into place Adjust the height of the grille frame via slots in brackets so the frame fits nicely against the under side of the ceiling Once the desired height is achieved tighten each M6 bolt in place locking the grille frame into the correct position Adjusting the Separator Plate Within the air curtain there is a s...

Page 7: ...odels Ambient units are supplied with a remote switch unit The switch unit allows the air curtain to be powered ON OFF and select one of three fan speeds Multiple Installation Ecopower only To Master Slave two or more air curtains together the remote control is plugged into the Master unit and a RJ lead should be connected from the Master to the Slave unit s Thermoscreens 3m RJ extension leads are...

Page 8: ...nsor thermistor on all units to be measuring DIP3 OFF Overheat Fan Disable If DIP4 is on and thermal overheat trips heat and fan circuits are isolated and LED s on wall switch flash If DIP4 is off and TOC trips out only the heat circuit is isolated and the LED s on the wall switch flash DIP4 Option Electric only Wall switch upgrade required The handset has to be powered on Independently set up DIP...

Page 9: ... contact the unit will run If it is open circuit across the terminal the unit will switch off This remote On Off feature has global switching logic i e if you master slave several units together you need connect the remote contact to only one of them to turn all units on and off in the master slave system As supplied a wire link will be fitted to the terminal block on every unit For summer setting...

Page 10: ...4001150 6 Page 10 of 128 ...

Page 11: ...4001150 6 Page 11 of 128 ...

Page 12: ...4001150 6 Page 12 of 128 ...

Page 13: ...r LED shows which fan speed is selected In Auto Mode the air curtain measures the incoming air temperature and automatically selects the necessary amount of heat to keep it at the level selected Heating level indicator LED s go from 0 to 100 in 8 steps to show the level selected In Manual Mode heat output can be selected as Zero Half Heat or Full Heat Heating level indicator LED s go 0 50 or 100 t...

Page 14: ...ault with electrical heated air curtains the thermal cut out s may operate Note If the mains supply is isolated during operation then the thermal cut outs may operate The thermal cut out s are located within the unit directly above the electric element banks one on the 1 1 5m and two on the 2m model There are two fuses on the Ecopower circuit board which may blow in the event of a fault For Ambien...

Page 15: ...ct Installer Service Agent to investigate why thermal cut out s have operated Service Agent to reset thermal cut out s Contact Installer Yes No Yes Yes No No No Yes Yes No No Is Electrical Power switched on Are the fans operating correctly Is the unit discharging warm air Check if thermal cut out s have tripped Electric Heated only Do the LED s light up on the remote control Is the remote control ...

Page 16: ...clean the build up of dirt and debris within the air curtain please note that the motor s are permanently lubricated and require no additional lubrication Once the air curtain has been cleaned check all electrical connections within the unit ensuring terminals are tight and that crimped connections have not become loose Re install the recessed grille ensuring the straight louvers are directly unde...

Reviews: