DIP switches fitted on the Ecopower board provide a selection of optional features as described above. Isolate and
switch electrical power off before configuring and/or changing any DIP switch settings.
•
Easy plug-in arrangement for remote air sensor thermistor on a 1m lead. Plugging-in the remote air sensor to J3
disables the standard air sensor thermistor already fitted on the Ecopower board. As supplied, the board will not have
the remote air sensor fitted.
•
An INHIBIT two screw terminal fitted on the Ecopower board for BMS remote On/Off feature.
If the terminal is linked, i.e. by 2 wires to a remote volt free contact, the unit will run. If it is open circuit across the
terminal the unit will switch off. This remote On/Off feature has global switching logic, i.e. if you master/slave several
units together you need connect the remote contact to only one of them to turn all units on and off in the master/slave
system. As supplied, a wire link will be fitted to the terminal block on every unit. For summer settings place a 3.3k
Ω
resistance across the INHIBIT terminal, with these settings fans only will run even if controller is requesting for heat.
ECOPOWER BOARD
Customer Building Management System
•
A HEALTHY two screw terminal is included on the board for a fault signal indication if the electric elements overheat
cut-out has operated. A healthy system provides a 24V DC signal at the terminals compared to an overheat fault which
provides OV DC.