  Fitting of the Recessed Grille

 

 

The

 

grille consists of a frame, grille core (fitted 

within the frame) and four brackets (note: the 
brackets are fixed to the frame). 

 

 

Removal of Grille Core 

 

Prior to fitting the grille to the air curtain and the 
ceiling the grille core will need to be removed from 
its frame.  Release the grille core by unfastening 
the two conical bolts fitted at each end of the grille 
core.  Push against the spring loaded pins and the 
grille core can now be pulled clear of its frame.  

 

Note: the grille core will still be attached to the 
frame via cord safety ties. 
 

The rectangular hole in the ceiling must be 
sized to suit the grille frame, see Figure 1 
for dimensions. 

 
 

  Attaching the Grille to the Air Curtain 

 

Before lifting the grille frame into position locate the four M6 bolts (two inside each end 
of the air curtain). Remove the M6 bolts and lift the frame into position (ensure that 
when fitted the air discharge vanes align with the air discharge of the air curtain, see 
Figure 1), screw each M6 bolt through the slot in the grille bracket until all four are 
located into place. Adjust the height of the grille frame (via slots in brackets) so the 
frame fits nicely against the under side of the ceiling. Once the desired height is 
achieved tighten each M6 bolt in place locking the grille frame into the correct position. 
 

  Adjusting the Separator Plate 

 

Within the air curtain there is a sliding separator plate, 
this needs adjusting up or down to stop the air 
discharge re-circulating within the air curtain. To adjust 
the separator plate release the M6 bolts at either end, 
extend the slide plate so that it will just touch the 
topside of the grille along its whole length and tighten 
the bolts. It will be necessary to fit the grille core to 
gauge where the separator plate should be fitted. 
 

  Fitting the Grille Core 

 

Once the above is complete the grille core can be refitted, to do so locate each spring 
loaded pin in its locating hole, push against the spring loaded pins to allow the fixed 
pins to locate within their fixing holes.  Tighten and secure the conical bolts fitted at 
each end of the grille core. 

 

Once the ceiling is finished remove the protective plastic film from the recessed grille 
frame. 

Summary of Contents for C1000AR

Page 1: ...4001150 6 Page 1 of 128 C RECESSED RANGE AIR CURTAINS INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION ...

Page 2: ...ote Control Ecopower Electric LPHW Manual Ambient Recessed Grille If anything is missing or damaged please contact your place of purchase immediately For your records Date of Purchase Place of Purchase Serial Number For warranty purposes proof of purchase is necessary so please keep a copy of your invoice All documentation supplied with each unit should be stored and kept for future reference ...

Page 3: ...ll need an air ventilation grille of effective free area cm2 as given in Table 1 and an adequate air path within the void for air to enter the punched air ventilation slots Table 1 Air curtain Required air flow within ceiling void m3 hr Effective free area of ventilation grille for an enclosed ceiling void cm2 C1000R 353 500 C1500R 421 700 C2000R 707 1200 Ceiling Suspension Make the cut out in the...

Page 4: ...29 A mm 1529 C2000R 2040 2090 1209 1609 2120 C 353 CEILING LEVEL 257 B 206 Electrical supply inlet 22 A 301 33 165 1m 140 1 5m 140 2m 150 Figure 1 Length mm Width mm Cut Out in Ceiling 1579 1179 2090 311 311 311 LPHW connections Rp 1 2 1 2 BSP female 22 25 85mm ...

Page 5: ...Electrical Input must be rated IP21 or higher Table 2 Air Curtain Electrical Supply V ph Hz Rated Power Input kW Current per phase A Heat Output kW Weight kg C1000AR 230 1 50 0 15 0 7 N A 19 C1500AR 230 1 50 0 20 0 9 N A 25 C2000AR 230 1 50 0 25 1 1 N A 35 C1000WR 230 1 50 0 15 0 7 6 0 20 C1500WR 230 1 50 0 20 0 9 9 0 27 C2000WR 230 1 50 0 25 1 1 12 0 37 C1000ER 400 3 50 9 15 13 7 4 5 9 0 22 C1500...

Page 6: ...crew each M6 bolt through the slot in the grille bracket until all four are located into place Adjust the height of the grille frame via slots in brackets so the frame fits nicely against the under side of the ceiling Once the desired height is achieved tighten each M6 bolt in place locking the grille frame into the correct position Adjusting the Separator Plate Within the air curtain there is a s...

Page 7: ...odels Ambient units are supplied with a remote switch unit The switch unit allows the air curtain to be powered ON OFF and select one of three fan speeds Multiple Installation Ecopower only To Master Slave two or more air curtains together the remote control is plugged into the Master unit and a RJ lead should be connected from the Master to the Slave unit s Thermoscreens 3m RJ extension leads are...

Page 8: ...nsor thermistor on all units to be measuring DIP3 OFF Overheat Fan Disable If DIP4 is on and thermal overheat trips heat and fan circuits are isolated and LED s on wall switch flash If DIP4 is off and TOC trips out only the heat circuit is isolated and the LED s on the wall switch flash DIP4 Option Electric only Wall switch upgrade required The handset has to be powered on Independently set up DIP...

Page 9: ... contact the unit will run If it is open circuit across the terminal the unit will switch off This remote On Off feature has global switching logic i e if you master slave several units together you need connect the remote contact to only one of them to turn all units on and off in the master slave system As supplied a wire link will be fitted to the terminal block on every unit For summer setting...

Page 10: ...4001150 6 Page 10 of 128 ...

Page 11: ...4001150 6 Page 11 of 128 ...

Page 12: ...4001150 6 Page 12 of 128 ...

Page 13: ...r LED shows which fan speed is selected In Auto Mode the air curtain measures the incoming air temperature and automatically selects the necessary amount of heat to keep it at the level selected Heating level indicator LED s go from 0 to 100 in 8 steps to show the level selected In Manual Mode heat output can be selected as Zero Half Heat or Full Heat Heating level indicator LED s go 0 50 or 100 t...

Page 14: ...ault with electrical heated air curtains the thermal cut out s may operate Note If the mains supply is isolated during operation then the thermal cut outs may operate The thermal cut out s are located within the unit directly above the electric element banks one on the 1 1 5m and two on the 2m model There are two fuses on the Ecopower circuit board which may blow in the event of a fault For Ambien...

Page 15: ...ct Installer Service Agent to investigate why thermal cut out s have operated Service Agent to reset thermal cut out s Contact Installer Yes No Yes Yes No No No Yes Yes No No Is Electrical Power switched on Are the fans operating correctly Is the unit discharging warm air Check if thermal cut out s have tripped Electric Heated only Do the LED s light up on the remote control Is the remote control ...

Page 16: ...clean the build up of dirt and debris within the air curtain please note that the motor s are permanently lubricated and require no additional lubrication Once the air curtain has been cleaned check all electrical connections within the unit ensuring terminals are tight and that crimped connections have not become loose Re install the recessed grille ensuring the straight louvers are directly unde...

Reviews: