24
Table 6.1:
Main Menu Options
Menu Option
Applies To
Set-Point/Settings Available
Range/Options
Precision
MAINTAIN
TEMPERATURE
Individual
Circuit
MAINTAIN TEMPERATURE
-129°C to 600°C; -200°F to 1112°F (LOW
TEMP ALARM to HIGH TEMP ALARM)
*see
Section 7.4
for Ambient setting
1°
BANDWIDTH (Control Band)
1°C to 300°C; or 1°F to 300°F
1°
RTD SETTINGS
Individual
Circuit
NUMBER OF RTDS
1 or 2
RTD FAULT POWER
0 – 100%
1 %
HIGH TEMP
ALARMS
Individual
Circuit
TRIP or HIGH (HIGH is a higher level
alarm if HIGH TEMP TRIP is OFF)
HIGH TEMP ALARM to 1112°F or 600°C
1°
ALARM
MAINTAIN TEMP+BA1 to HIGH
TEMPERATURE TRIP (HIGH)
1°
HIGH TEMP SEEN
RESET = Y or N
1°
LOW TEMP
ALARM
Individual
Circuit
LOW TEMP ALARM
-200°F or -200°C to MAINTAIN TEMP
1°
LOW TEMP SEEN
RESET = Y or N
1°
GROUND
CURRENT
Individual
Circuit
GROUND CURRENT (real-time
ground/earth fault current
measurement)
0-225 mA
1 mA
TRIP or HIGH (HIGH is a higher level
alarm if GROUND CUR TRIP is OFF)
GROUND CURRENT ALARM to 225 mA
1 mA
GROUND CURRENT ALARM
20 to GROUND CURRENT TRIP (HIGH)
1 mA
HEATER
CURRENT
Individual
Circuit
HEATER CURRENT (real-time heater
current measurement)
0.0 A to 240.0 A
0.1 A
HEATER POWER CLAMP (FOR
ON/OFF SSR only)
0 – 100%
1 %
HIGH CURRENT
ALARMS
Individual
Circuit
TRIP or HIGH (HIGH is higher level
alarm if HEATER CUR TRIP is OFF
HIGH CURRENT ALARM to 245.0 A
0.1 A
ALARM
1.0 A to HIGH CURRENT TRIP (HIGH)
0.1 A