9
3
Module Connections
& Wiring
The TCM2 is intended for use exclusively in TraceNet TCM2 Control and
Monitoring System panels. Refer to
Figures 3.1
and
3.2
for TCM2 Module
connections.
Design considerations within panel:
Control wiring is rated to 105°C
GFI test loop wires should be passed through their corresponding GFI
CT’s
Alarm digital outputs are intended to drive internal signal relays or lights
and should not be directly connected to field wiring
Care must be taken to avoid exceeding the temperature rating of the
TCM2. Refer to
Table 2.3
for panel current ratings.
3.1 Bottom Side Connections
1. POWER: Mains supply input accepts 100 – 240 V~, at 50/60 Hz. L1 is
Line 1, L2 is Line 2 or Neutral, and the symbol
is the protective
conductor/ground connection.
2. 24 VDC & DIGITAL OUTPUTS: A 24 VDC output is provided to power
accessories such as a serial to Ethernet converter. The output supplies
up to 9 W and is over-current protected. The Digital outputs provide
alarm functionality. Each 24 VDC output is current limited to 100 mA.
Figure
3.1:
Bottom-Side Connections