40
Table 12.6:
Read Only Controller Data
Function
Code(s)
Address
Description
Values
03
2008
Language
0 = English;
1 = Spanish;
2 = Russian;
03
2009
Password
0000 – 9999
03
2010
Password Enable
0 = Disabled;
1 = Enabled
03
2011
TCM2 Type
0 = 2-circuit (Default)
1 = 1-circuit, 1 CT;
2 = 1-Circuit, 2 CTs;
3 = 1-Circuit, 3 CTs
03
2012
Serial number low
03 2013
Serial number med
03 2014
Serial number high
2015
No Data Here
03 2016
Circuit Offset
2017
No Data Here
03 2018
Screen Saver
2019
Max Off Current
03
2020-2021
No Data Here
03 2022
Relay Output Voltage
0 = 12 V; 1 = 24 V
2023
No Data Here
2024
Hours in Use
03 2025
Start Up Delay
2026
Soft Start
03
2027
Ground/Earth Fault Sensitivity
0 = Most Sensitive;
3 = Least Sensitive
2028-2030
No Data Here
03 2031
Single Temp Alarms
Should always = 0
03 2032
High Temp Alarm Delay
2033-2035
No Data Here
03
2036
Alarm Relay Type
0 = Normally OFF;
1 = Normally ON
2037
Alarm Relay Masking
2038
No Data Here
03 2039
Firmware Version Number
2040-2043
No Data Here
03 2044
Self-Test Hours
2045
Start self-Test
Non-zero Starts a self-test
03 2046
Units
0 = F; 1 = C