![Thermon TraceNet TCM2 Installation, Start-Up, Operating And Maintenance Manual Download Page 10](http://html1.mh-extra.com/html/thermon/tracenet-tcm2/tracenet-tcm2_installation-start-up-operating-and-maintenance-manual_1105829010.webp)
5
2
Specifications
TCM2 control panels are available in a variety of configurations. The table below
serves as general specification information for these control panels.
Table 2.1:
TCM2 Panel Specifications
Parameter
Description
Heat Trace Mains Supply
100 to 600 V~, 50/60 Hz (See
Table 2.2
for Control
Module supply information)
Control Points
Up to 2 Heat Tracing Circuits
Heat Trace Current
See
Table 2.3
:
Maximum
Heater
Current
Through
Each
Solid
State
Relay
Temperature Inputs
Up to Two per Control Point; Platinum RTDs 100
Ω
@ 32 °F (0 °C)
Temperature Control
Range
-200 °F to 1112 °F (-129 °C to 600 °C)
Alarm Contact Relays
24 VDC, 200 mA
Communication
RS-485 , ModBus ASCII or RTU, up to 57600 Baud
Control Methods
On/Off MEC, On/Off SSR, Proportional, Ambient or
APCM
Display
4 Line, 20 Character, OLED
Relative Humidity
0 to 90% Non-Condensing
Exterior Panel Operating
Temperature
-40 °F to 104 °F (-40 °C to 40 °C)
Interior Operating
Temperature
-40 °F to 140 °F (-40 °C to 60 °C)
Storage Temperature
-40 °F to 140 °F (-40 °C to 60 °C)
Dimensions (W x H x D)
See
Table 2.4