background image

4

Section 1: Genesis Introduction and 

Overview

 

The following serves as a general guide and overview on 

the installation, startup, operation, and maintenance of a 

TraceNet Genesis heat tracing control panel. This guide is 

to be sent in conjunction with the project specific panel 

drawings  and  any  other  installation  instructions/guides 

and standards provided. In the unlikely event that a conflict 

or  uncertainty  arises,  contact  the  Thermon  engineering 

support personnel assigned to this project to clarify. 
NOTE:  All  personnel  should  be  properly  trained  and 

qualified  to  safely  install,  service,  operate,  and  program 

this TraceNet heat tracing control panel as well as to install, 

operate, and maintain all associated heat tracing. 

Section 2: Panel Inspection, Field 

Connections and Internal Wiring

 

A typical Genesis Panel may include electrical distribution 

(optional  main  breaker  with  branch  breakers  for  each 

electrical heating circuit, either within the Genesis panel 

or in an adjacent electrical distribution enclosure. (Refer to 

the project specific drawings for each panel.) 
Wide  varieties  of  TraceNet  Genesis  panel  configurations 

are  possible  and  can  be  located  in  site  locations  having 

electrically classified areas and/or ordinary locations. The 

actual panel markings provided with the panel will detail 

the approvals for the specific location of the panel. 

2.1: Recommended Visual Inspection Procedures

 

• 

Inspect  door  and/or  solid  state  heat  sink  gaskets  for 

water  intrusion  as  indicated  by  mineral  deposits  and 

rust. Where feasible replace any gaskets which appear 

to be faulty. 

• 

Survey panel exterior and interior for dust, lint, moisture, 

or foreign residue. Remove any such residue with a lint 

free cloth material. Heavy residues may be addressed 

with wood scrapers and a cleaning agent. Do not soak 

parts with cleaning agent but only use dampened cloths 

in  removing  heavy  residues.  Excessive  application  of 

cleaning agents can damage components.

• 

Check  for  panel  corrosion  and  scratches.  Remove 

corrosion  and  prepare  any  damaged  areas  with 

sandpaper.  Repaint  with  the  approved  primer  and 

touch up paint.

• 

Check  door  hinges,  latches,  and  other  moving  parts 

for proper operation. Use machine oil to lubricate the 

moving  parts  and  restore  proper  operation  where 

necessary. 

• 

Check for mechanical damage to any windows as well 

as check the window seals. Repair or replace damaged 

materials.  In  all  cases  where  equipment  damage  is 

observed,  a  root  cause  analysis  should  be  initiated 

to  determine  any  future  corrective  action  needed  to 

prevent a recurrence. 

2.2: Wiring and Connections Survey 

• 

The wiring and connections survey recommended is as 

follows: 

• 

If  the  servicing  of  removable  electrical  connectors  is 

to be conducted, then make certain the area is free of 

explosive atmospheres.

• 

If equipment is available, an infrared scan of the interior 

of  the  panel  cabinet  and  associated  wiring  (during 

operation) is recommended. 

• 

Any  unusually  high  temperatures  at  connections 

are  usually  evidence  of  poor  connections.  Tighten 

connections,  repair  with  new  terminations,  and/or 

replace any components which have been exposed to 

long term overheating. All terminal block connections 

should  be  tightened  using  a  torque  indicating  screw 

driver  to  the  levels  indicated  in  Table  1  and  project 

installation drawings. 

• 

Check  for  corrosion  at  electrical  connections  and 

terminations.  Where  corrosion  of  electrical  terminals 

is  observed,  this  may  be  additional evidence  of  loose 

connections  and  excessive  heat.  A  part  replacement 

may be necessary. 

• 

Inspect wiring for abrasion wear, mechanical damage, 

and  thermal  overexposure.  Repair  or  replace  any 

damaged  or  defective  wiring.  In  all  cases  where 

equipment damage is observed, a root cause analysis 

should be initiated to determine any future corrective 

action needed to prevent a recurrence. 

2.3: Control System Operation Check

 

The  Genesis  controller  screen  is  an  ideal  resource  in 

facilitating operation checks of the control system. To begin 

this program, energize the panel and the appropriate heat 

trace circuits for a minimum of 24 hours or until all circuits 

are cycling within their appropriate control band. A typical 

list of operational maintenance checks are available for a 

successful installation of a TraceNet Genesis heat tracing 

control and monitoring panel, a number of equally critical 

parts  of  the  system  must  be  installed  properly.  Areas 

requiring close attention are:

• 

The heat trace and insulation

• 

The RTD temperature sensor installation

• 

The distribution of the field RTD and power wiring

• 

The installation and routing of wiring inside the TraceNet 

panel. 

Note:

  The  heat  tracing  system  installation  shall  be  in 

accordance with the electrical area classification requirements 

as well as shall conform to the latest requirements as detailed 

in applicable heat tracing standards, the local Electrical Code 

and plant standard practices. Where conflicts arise, contact the 
project engineer for resolution. 

Summary of Contents for Tracenet Genesis

Page 1: ...TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM Installation Operation Maintenance Guide...

Page 2: ...ts in workmanship or material under normal use and service If any part of the equipment proves to be defective in workmanship or material and if such part is within 12 months of the date of shipment f...

Page 3: ...ples 16 4 1 Line Sensing Control 16 4 2 Ambient Sensing Options 16 4 3 Proportional Control and Power Clamp 17 Section 5 Genesis Testing and Start Up 17 Section 6 Operation and Maintenance of the Gene...

Page 4: ...materials In all cases where equipment damage is observed a root cause analysis should be initiated to determine any future corrective action needed to prevent a recurrence 2 2 Wiring and Connections...

Page 5: ...response curve type is coordinated with the startup characteristic of the heat trace cable in a cold start condition All distribution wiring connections should be tightened using a torque indicating...

Page 6: ...ay but the Genesis HMI will not be able to distinguish individual circuit segments from a common control relay 3 1 3 The DTM The DTM Distributed Temperature Module is a DIN rail mountable six RTD sens...

Page 7: ...o sense 24 Vdc supplied by the IOM through an open or closed relay contact This allows input from various types of signals from 0 Vdc to 24 Vac As long as the coil side of the relay used is appropriat...

Page 8: ...move between circuits touch the circuit dot drag the black selector around the dial or use the arrows on either side of the circuit number The center of the dial displays the highlighted circuit s liv...

Page 9: ...tempting to change any setting or set point or Admin Login may be selected from the Menu Admin mode is indicated by the red tint and red boarder on and around all screens The system will remain in Adm...

Page 10: ...fault loop test and additionally turns measures heater current with heater on and off to verify relay operation and current measurements Touch to Start Mechanical Relay Duty Cycle Time Duty cycle per...

Page 11: ...e will be displayed if the measured heater current is higher than the HIGH CURRENT TRIP HIGH set point 5 HIGH CURRENT ALARM The measured heater current rise is higher than the HIGH CURRENT ALARM set p...

Page 12: ...total of Watts accumulated since last reset of value Number 0 2 147 483 648 Watts Time Heater Will Come Back On Applies to APCM time left until the heater switches on again Number 0 32 Minutes Ground...

Page 13: ...companying set point changes 3 2 8 Circuit ISO Use multi touch pinch and zoom gestures to view the ISO isometric drawing for the circuit 3 2 9 Circuit Notes Useful notes can be stored here for any pur...

Page 14: ...dual alarm or all alarms for that circuit can be acknowledged 3 2 12 Import Export The Import Export feature is used to load isometrics and to import and export system configuration files to easily an...

Page 15: ...alternate breaker and control relay it s best to have the heater reassigned to the desired breaker relay and identified at the HMI see section 3 2 6 Circuit Settings The recommended DCM code range is...

Page 16: ...h APC the heat trace will be set to operate at 100 power continuously on at the minimum ambient temperature and reduce power as the ambient temperature rises to the maintain temperature When the ambie...

Page 17: ...p Section 6 Operation and Maintenance of the Genesis Control and Monitoring System 6 1 Maintenance Preventive maintenance consists of inspection testing checking connections and general cleaning of eq...

Page 18: ...and monitor heat tracing circuits The following steps show navigation of the controller s basic functions TraceNetTM Genesis CONTROL AND MONITORING SYSTEM OVERVIEW HAMBURGER MENU The Overview screen d...

Page 19: ...justments to circuit level or updates to global settings Select Global Settings to adjust how the Genesis displays system wide variables such as language temperature system time Select Import Export t...

Page 20: ...20 Appendix B Genesis Specifications Guide With Component Limits And Specifications TRACENETTM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE...

Page 21: ...r nonhazardous locations hazardous locations and Purge for hazardous locations IEC EN UL CSA 61010 1 Ex ec IIC T4 Gc II 3 Ex ec IIC T4 Gc Class I Division 2 Groups ABCD T4 Class I Zone 2 Group IIC T4...

Page 22: ...thernet USB Maximum storage temperature 85 C 185 F Minimum storage temperature 40 C 40 F Operating ambient temperature range 40 C 40 F to 70 C 158 F HMI DIMENSIONAL DATA HMI PRODUCT FEATURES TraceNet...

Page 23: ...up to 20 RTD s per circuit Monitors ground earth leakage and heater operating current in heat tracing circuits DCM COMPONENT SPECIFICATIONS Circuit control capacity up to six heat trace circuits Stor...

Page 24: ...ensors LED Identifier To Address Configurable Input Output Channels RTD Inputs DTM DIMENSIONAL DATA 41 mm 1 5 8 111 mm 4 3 8 77 mm 3 IOM INPUT OUTPUT MODULE The IOM is a DIN rail mountable input outpu...

Page 25: ...ystems communicate via Ethernet to the plant DCS The same operating data and control capabilities that are available through TraceNet Command are also accessible in the plant control room at the DCS C...

Page 26: ...puts 18 36 54 72 108 144 Distribution ND No Distribution MBx BF y z Main Breaker Breaker Frame Capacity Number of Breakers Thermon Part Number Location O Ordinary Locations H1 Class Division Hazardous...

Page 27: ...100 Thermon Dr PO Box 609 San Marcos TX 78667 0609 Phone 512 396 5801 1 800 820 4328 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Page 28: ...ide by and compare to insulation diameter charts for proper over sizing Check insulation type and thickness against design specification Replace insulation or review system design for alternate operat...

Page 29: ...emperature sensor Is RTD sensor next to pipe support equipment or other heat sink Move RTD sensor to location more representative of the majority of the piping Improperly installed RTD temperature sen...

Page 30: ...er address duplicate addresses or improper configuration of firmware software Change controller address or reconfigure firmware software Loose or open connection in RS485 line Recheck for continuity i...

Page 31: ...anticipated in the design stage Verify installed length if possible and if different review design If length is different but performance wise the as built design is acceptable initiate as built draw...

Page 32: ...ferent review design If length is different but performance wise the as built design is acceptable initiate as built drawing change and change controller low current setting Check heater set tags or m...

Page 33: ...r wiring of current sense wires through toroid The current sensing toroid must have the outgoing heater current lead and the return current heater lead run through the toroid for a proper ground leaka...

Page 34: ...0001 bit Low temperature Alarm 03 06 101 0x0065 Maintain temp 10x True Value 03 06 102 0x0066 Control Band 10x True Value 03 06 103 0x0067 High Temperature Trip Alarm 03 06 104 0x0068 High Temp Alarm...

Page 35: ...x0800 bit RTD Fault No Communication for all assigned RTD s 0x0400 bit High Temperature trip 0x0200 bit RTD Fault all assigned RTD s in fault 0x0100 bit Not Used 0x0080 bit High Current 0x0040 bit Low...

Page 36: ...ers 7171 Southwest Parkway Building 300 Suite 200 Austin TX 78735 Phone 512 690 0600 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Reviews: