background image

11

Set-point

Description

Available Options

Lower Limit

Lower Bound

Upper Bound

Upper 

Limit

Units

Circuit Information

Circuit Number

Number of the circuit within the panel

Read-Only

1

72

None

Circuit Tag

Alpha-numeric Identifier

Read-only in Dashboard, User-

defined in Settings

50

Characters

Circuit Status

Percent On (Duty-Cycle); Enable Button

Disabled, Enabled, Enabled 

Forced-On, Enabled Forced-Off

100

%

Temperature

High High Alarm/

 

High Temp Trip

1

High High Alarm: If Temperature Trip is disabled. 

 

High Trip: If Temperature Trip is enabled

User-Defined

-200 (-328)

High Temperature 

Alarm Set Point

Upper Limit

650

 

(1200)

°C (°F)

High Temp Alarm

2

High Temperature Alarm activates at and 

above this set point

User-Defined

-200 (-328)

Max + 1

High High Alarm/

 

High Trip Set point

650

 

(1200)

°C (°F)

Max

Above Max heater duty cycle is 0%, i.e. 

Heater is off

User-Defined

1

1

High Alarm set point - 

Maintain set point - 1

650

 

(1200)

°C (°F)

Temperature

Real-time Temperature measurement

Read-only Measurement

-200 (-328)

650

 

(1200)

°C (°F)

Maintain

Set point at and below which heater duty 

cycle is 100%

User-Defined

-200 (-328)

Low Alarm set 

point + 1

Max - 1

650

 

(1200)

°C (°F)

Low Alarm

3

Low Temperature Alarm activates at and 

below this set point

User-Defined

-200 (-328)

Lower Limit

Maintain 

 

Temperature - 1

650

 

(1200)

°C (°F)

Notes:
1.

  HIGH TEMP TRIP (HIGH HIGH TEMP) If HIGH TEMPERATURE TRIP is ON (OFF), this message will be displayed if the measured temperature rises above a value equal to the HIGH TEMPERATURE TRIP (HIGH) set-point.

2.

  HIGH TEMP ALARM The measured temperature has risen above a value equal to the HIGH TEMPERATURE ALARM set-point but has not yet risen above a value equal to the HIGH TEMPERATURE TRIP/HIGH set-point. 

3.

  LOW TEMP ALARM The measured temperature has fallen below a value equal to the LOW TEMPERATURE ALARM set-point.

Heater Current

High High Alarm/

 

High Current Trip

4

High High Alarm: If Current Trip is disabled. 

 

High Trip: If Current Trip is enabled

User-Defined

0

High Alarm

Upper Limit

100

A

High Current 

Alarm

5

High Current Alarm activates at and above 

this set point

User-Defined

0

Low Alarm + 1

High High Alarm/

High Trip

100

A

Low Current 

Alarm

6

Low Current Alarm activates at and below 

this set point

User-Defined

0

High Alarm set 

point - 1

100

A

Notes:
4.

  HIGH CURRENT TRIP (HIGH HIGH AMPS) If HIGH CURRENT TRIP is ON (OFF), this message will be displayed if the measured heater current is higher than the HIGH CURRENT TRIP (HIGH) set-point. 

5. 

HIGH CURRENT ALARM The measured heater current rise is higher than the HIGH CURRENT ALARM set-point but not above the HIGH CURRENT TRIP/HIGH.

6.

  LOW CURRENT ALARM The measured heater current has fallen lower than the LOW CURRENT ALARM set-point.

Ground Current

High High Alarm/

 

High Leakage Trip

7

High High Alarm: If Ground Trip is disabled. 

 

High Trip: If Ground Trip is enabled

User-Defined

20

High Alarm

Upper Limit

255

mA

High Leakage 

Alarm

8

High Ground Fault Current Alarm activates 

at and above this set point

User-Defined

20

Lower Limit

High High Alarm/

High Trip

255

mA

Notes:
7.

  HIGH LEAKAGE TRIP (HIGH HIGH GROUND) If GROUND CURRENT TRIP is ON (OFF), this message will be displayed if the measured ground/earth leakage current rises above the GROUND CURRENT TRIP (HIGH) set-

point.  

8.

  HIGH LEAKAGE ALARM The measured ground/earth leakage current has risen above the GROUND CURRENT ALARM set-point but not above the GROUND CURRENT TRIP/ALARM2 set-point.

3.2.5: Dashboard/Circuit Details

The dashboard provides a comprehensive single circuit view. It includes the circuit 

number, tag, pipeline number, or other status as well as real-time temperature, 

heater current, ground leakage current and related alarm set points. This screen 

can be reached by tapping a circuit in the Overview or the Circuit List. The limits 

below define the lowest and highest possible values. (The bounds define the 

constraints for valid values, e.g. maintain temperature should not be set below 

the low temperature alarm.)
Circuit Alarms 
In the event that the measured conditions of the heat trace circuit fall outside 

the user-defined parameters, the Genesis will notify the user. When an alarm 

condition first occurs, the common alarm digital output will annunciate and a 

message will appear on the Circuit Screen to inform the user of the type of alarm 

present. Pressing will acknowledge the alarm and deactivate the digital output. 

Alarms will automatically clear when the alarm condition is no longer present. 
Circuit Trips 
In the event that the measured conditions of the heat trace circuit go beyond the 

TRIP settings of the circuit, the circuit will trip, i.e. turn off. When a circuit trips, 

the circuit will be deactivated and a corresponding message will be displayed. 

(A TRIP event is different from an ALARM event in that the heat trace circuit is 

deactivated and will remain deactivated until the circuit is manually reset by the 

user.)

Summary of Contents for Tracenet Genesis

Page 1: ...TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM Installation Operation Maintenance Guide...

Page 2: ...ts in workmanship or material under normal use and service If any part of the equipment proves to be defective in workmanship or material and if such part is within 12 months of the date of shipment f...

Page 3: ...ples 16 4 1 Line Sensing Control 16 4 2 Ambient Sensing Options 16 4 3 Proportional Control and Power Clamp 17 Section 5 Genesis Testing and Start Up 17 Section 6 Operation and Maintenance of the Gene...

Page 4: ...materials In all cases where equipment damage is observed a root cause analysis should be initiated to determine any future corrective action needed to prevent a recurrence 2 2 Wiring and Connections...

Page 5: ...response curve type is coordinated with the startup characteristic of the heat trace cable in a cold start condition All distribution wiring connections should be tightened using a torque indicating...

Page 6: ...ay but the Genesis HMI will not be able to distinguish individual circuit segments from a common control relay 3 1 3 The DTM The DTM Distributed Temperature Module is a DIN rail mountable six RTD sens...

Page 7: ...o sense 24 Vdc supplied by the IOM through an open or closed relay contact This allows input from various types of signals from 0 Vdc to 24 Vac As long as the coil side of the relay used is appropriat...

Page 8: ...move between circuits touch the circuit dot drag the black selector around the dial or use the arrows on either side of the circuit number The center of the dial displays the highlighted circuit s liv...

Page 9: ...tempting to change any setting or set point or Admin Login may be selected from the Menu Admin mode is indicated by the red tint and red boarder on and around all screens The system will remain in Adm...

Page 10: ...fault loop test and additionally turns measures heater current with heater on and off to verify relay operation and current measurements Touch to Start Mechanical Relay Duty Cycle Time Duty cycle per...

Page 11: ...e will be displayed if the measured heater current is higher than the HIGH CURRENT TRIP HIGH set point 5 HIGH CURRENT ALARM The measured heater current rise is higher than the HIGH CURRENT ALARM set p...

Page 12: ...total of Watts accumulated since last reset of value Number 0 2 147 483 648 Watts Time Heater Will Come Back On Applies to APCM time left until the heater switches on again Number 0 32 Minutes Ground...

Page 13: ...companying set point changes 3 2 8 Circuit ISO Use multi touch pinch and zoom gestures to view the ISO isometric drawing for the circuit 3 2 9 Circuit Notes Useful notes can be stored here for any pur...

Page 14: ...dual alarm or all alarms for that circuit can be acknowledged 3 2 12 Import Export The Import Export feature is used to load isometrics and to import and export system configuration files to easily an...

Page 15: ...alternate breaker and control relay it s best to have the heater reassigned to the desired breaker relay and identified at the HMI see section 3 2 6 Circuit Settings The recommended DCM code range is...

Page 16: ...h APC the heat trace will be set to operate at 100 power continuously on at the minimum ambient temperature and reduce power as the ambient temperature rises to the maintain temperature When the ambie...

Page 17: ...p Section 6 Operation and Maintenance of the Genesis Control and Monitoring System 6 1 Maintenance Preventive maintenance consists of inspection testing checking connections and general cleaning of eq...

Page 18: ...and monitor heat tracing circuits The following steps show navigation of the controller s basic functions TraceNetTM Genesis CONTROL AND MONITORING SYSTEM OVERVIEW HAMBURGER MENU The Overview screen d...

Page 19: ...justments to circuit level or updates to global settings Select Global Settings to adjust how the Genesis displays system wide variables such as language temperature system time Select Import Export t...

Page 20: ...20 Appendix B Genesis Specifications Guide With Component Limits And Specifications TRACENETTM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE...

Page 21: ...r nonhazardous locations hazardous locations and Purge for hazardous locations IEC EN UL CSA 61010 1 Ex ec IIC T4 Gc II 3 Ex ec IIC T4 Gc Class I Division 2 Groups ABCD T4 Class I Zone 2 Group IIC T4...

Page 22: ...thernet USB Maximum storage temperature 85 C 185 F Minimum storage temperature 40 C 40 F Operating ambient temperature range 40 C 40 F to 70 C 158 F HMI DIMENSIONAL DATA HMI PRODUCT FEATURES TraceNet...

Page 23: ...up to 20 RTD s per circuit Monitors ground earth leakage and heater operating current in heat tracing circuits DCM COMPONENT SPECIFICATIONS Circuit control capacity up to six heat trace circuits Stor...

Page 24: ...ensors LED Identifier To Address Configurable Input Output Channels RTD Inputs DTM DIMENSIONAL DATA 41 mm 1 5 8 111 mm 4 3 8 77 mm 3 IOM INPUT OUTPUT MODULE The IOM is a DIN rail mountable input outpu...

Page 25: ...ystems communicate via Ethernet to the plant DCS The same operating data and control capabilities that are available through TraceNet Command are also accessible in the plant control room at the DCS C...

Page 26: ...puts 18 36 54 72 108 144 Distribution ND No Distribution MBx BF y z Main Breaker Breaker Frame Capacity Number of Breakers Thermon Part Number Location O Ordinary Locations H1 Class Division Hazardous...

Page 27: ...100 Thermon Dr PO Box 609 San Marcos TX 78667 0609 Phone 512 396 5801 1 800 820 4328 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Page 28: ...ide by and compare to insulation diameter charts for proper over sizing Check insulation type and thickness against design specification Replace insulation or review system design for alternate operat...

Page 29: ...emperature sensor Is RTD sensor next to pipe support equipment or other heat sink Move RTD sensor to location more representative of the majority of the piping Improperly installed RTD temperature sen...

Page 30: ...er address duplicate addresses or improper configuration of firmware software Change controller address or reconfigure firmware software Loose or open connection in RS485 line Recheck for continuity i...

Page 31: ...anticipated in the design stage Verify installed length if possible and if different review design If length is different but performance wise the as built design is acceptable initiate as built draw...

Page 32: ...ferent review design If length is different but performance wise the as built design is acceptable initiate as built drawing change and change controller low current setting Check heater set tags or m...

Page 33: ...r wiring of current sense wires through toroid The current sensing toroid must have the outgoing heater current lead and the return current heater lead run through the toroid for a proper ground leaka...

Page 34: ...0001 bit Low temperature Alarm 03 06 101 0x0065 Maintain temp 10x True Value 03 06 102 0x0066 Control Band 10x True Value 03 06 103 0x0067 High Temperature Trip Alarm 03 06 104 0x0068 High Temp Alarm...

Page 35: ...x0800 bit RTD Fault No Communication for all assigned RTD s 0x0400 bit High Temperature trip 0x0200 bit RTD Fault all assigned RTD s in fault 0x0100 bit Not Used 0x0080 bit High Current 0x0040 bit Low...

Page 36: ...ers 7171 Southwest Parkway Building 300 Suite 200 Austin TX 78735 Phone 512 690 0600 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Reviews: