background image

17

This is a less energy efficient approach to heat trace control, 

but is consistent with what is routinely provided with ambient 

sensing  mechanical  thermostats  controlling  a  contactor 

between  a  distribution panel’s  main circuit breaker  and the 

branch breaker panel board.

4.3: Proportional Control and Power Clamp

If “on/off with soft start” is selected with any Power Clamp 

percentage  other  than  100%  the  circuit  will  operate  as 

follows:

• 

Below the Low Temperature alarm (LTA) setpoint, the 

heater will be “full on” 100% of the time. 

• 

When  the  temperature  reaches/exceeds  the  LTA,  the 

soft start feature will energize the heater “full on” for 

the Power Clamp (time) percentage selected (n% of 1 

second) and over 90 seconds will ramp up to “full on” 

for 100% of the time.  

Regardless of what Power Clamp (time) percentage 

is selected, it will take a maximum of 90 seconds for 

the heater to be “full on” for 100% of the time.

The  heater  will  be  turned  off  once  the  Maximum 

Temperature  (Maintain  Temperature  plus  Control 

Band, or MT+CB) is reached, even if that temperature 

is reached in less than 90 seconds.

Once  the  heater  is  at  MT+CB  (Maximum 

Temperature),  it  will  continue  to  cycle  based  on 

the soft start settings.  In other words, once MT+CB 

is  reached  the  heater  is  de-energized  until  the 

temperature  drops  to  the  Maintain  Temperature 

(MT),  then  the  heater  will  be  energized  “full 

on”  starting  at  the  selected  Power  Clamp  (time) 

percentage (n%) and will go through the 90 second 

ramp up to “full on” for 100% of the time, or until 

the MT+CB is again reached.

Section 5: Genesis Testing and Start-Up 

All heat trace circuits should be properly terminated and 

megger  tested  prior  to  energizing  the  TraceNet  Genesis 

control panels. In addition, all pipes should be insulated 

with weather barrier to achieve the required temperatures 

to be maintained. 
Troubleshooting Tips
When starting up a newly installed heat trace and control 

system,  it  is  common  to  encounter  numerous  circuit 

alarms and possibly circuit “trip” events. Data entry errors, 

unanticipated temperature conditions and/or dead band 

settings that are too narrow, and other possible installation 

errors can be expected.   
A table of Troubleshooting Tips is provided in Appendix C 

to assist during start-up.

Section 6: Operation and Maintenance of 

the Genesis Control and Monitoring System

6.1: Maintenance

 

Preventive  maintenance  consists  of  inspection, 

testing,  checking  connections,  and  general  cleaning  of 

equipment  at  scheduled  intervals.  The  maintenance 

recommendations  that  follow  are  intended  to  support 

and in some cases “add to” those procedures detailed in 

the facility’s Planned Maintenance System (PMS). In case 

of  conflicts,  contact  the  project  engineer  for  resolution. 

When carrying out the scheduled maintenance program, 

the  following  safety  precautions  should  be  observed. 

Safety Precautions the heat tracing can be powered by the 

project specified nominal voltages ranging from 100 to 600 

Vac. It is important that only authorized trained personnel 

conduct these maintenance and service activities. Before 

conducting any maintenance or service procedure, exercise 

required lockout and tag out procedures at the appropriate 

circuit breakers. Additionally, do additional testing within 

the control panel to ensure that the specific heat tracing 

and control circuit of interest is fully de-energized and the 

equipment is grounded. If it becomes necessary to service 

or test live equipment, the following instructions must be 

followed: 

• 

Use one hand when servicing the equipment. Accidental 

death or severe injury may occur especially if a current 

path is created through the body from one hand to the 

other. 

• 

First,  de-energize  the  equipment.  To  de-energize  any 

capacitors  connected  into  the  circuits,  temporarily 

ground the terminals where work is to be done.

• 

Connect the multi-meter/instrument to the terminals of 

interest using a range higher than the expected. Make 

sure that you are not grounded whenever a need arises 

to adjust equipment or test circuit operation. Verify that 

all test equipment used is properly maintained and safe 

for the intended use. 

• 

Without touching the multi-meter/instrument energize 

the  equipment  and  read  the  values  indicated  on  the 

multi-meter/instrument. 

• 

Remove the test leads after de-energizing the circuit of 

interest. 

6.2: Maintenance Schedule Recommendation

 

The  service  schedule  is  somewhat  dependent  on  the 

“in  service”  hours.  As  a  general  rule,  however,  it  is 

recommended that the heat tracing control and monitoring 

panel be serviced on a twelve month basis to start. The 

schedule  may  be  adjusted  depending  on  the  operating 

history  of  the  panel  and  as  the  historical  maintenance 

records dictate. 

Summary of Contents for Tracenet Genesis

Page 1: ...TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM Installation Operation Maintenance Guide...

Page 2: ...ts in workmanship or material under normal use and service If any part of the equipment proves to be defective in workmanship or material and if such part is within 12 months of the date of shipment f...

Page 3: ...ples 16 4 1 Line Sensing Control 16 4 2 Ambient Sensing Options 16 4 3 Proportional Control and Power Clamp 17 Section 5 Genesis Testing and Start Up 17 Section 6 Operation and Maintenance of the Gene...

Page 4: ...materials In all cases where equipment damage is observed a root cause analysis should be initiated to determine any future corrective action needed to prevent a recurrence 2 2 Wiring and Connections...

Page 5: ...response curve type is coordinated with the startup characteristic of the heat trace cable in a cold start condition All distribution wiring connections should be tightened using a torque indicating...

Page 6: ...ay but the Genesis HMI will not be able to distinguish individual circuit segments from a common control relay 3 1 3 The DTM The DTM Distributed Temperature Module is a DIN rail mountable six RTD sens...

Page 7: ...o sense 24 Vdc supplied by the IOM through an open or closed relay contact This allows input from various types of signals from 0 Vdc to 24 Vac As long as the coil side of the relay used is appropriat...

Page 8: ...move between circuits touch the circuit dot drag the black selector around the dial or use the arrows on either side of the circuit number The center of the dial displays the highlighted circuit s liv...

Page 9: ...tempting to change any setting or set point or Admin Login may be selected from the Menu Admin mode is indicated by the red tint and red boarder on and around all screens The system will remain in Adm...

Page 10: ...fault loop test and additionally turns measures heater current with heater on and off to verify relay operation and current measurements Touch to Start Mechanical Relay Duty Cycle Time Duty cycle per...

Page 11: ...e will be displayed if the measured heater current is higher than the HIGH CURRENT TRIP HIGH set point 5 HIGH CURRENT ALARM The measured heater current rise is higher than the HIGH CURRENT ALARM set p...

Page 12: ...total of Watts accumulated since last reset of value Number 0 2 147 483 648 Watts Time Heater Will Come Back On Applies to APCM time left until the heater switches on again Number 0 32 Minutes Ground...

Page 13: ...companying set point changes 3 2 8 Circuit ISO Use multi touch pinch and zoom gestures to view the ISO isometric drawing for the circuit 3 2 9 Circuit Notes Useful notes can be stored here for any pur...

Page 14: ...dual alarm or all alarms for that circuit can be acknowledged 3 2 12 Import Export The Import Export feature is used to load isometrics and to import and export system configuration files to easily an...

Page 15: ...alternate breaker and control relay it s best to have the heater reassigned to the desired breaker relay and identified at the HMI see section 3 2 6 Circuit Settings The recommended DCM code range is...

Page 16: ...h APC the heat trace will be set to operate at 100 power continuously on at the minimum ambient temperature and reduce power as the ambient temperature rises to the maintain temperature When the ambie...

Page 17: ...p Section 6 Operation and Maintenance of the Genesis Control and Monitoring System 6 1 Maintenance Preventive maintenance consists of inspection testing checking connections and general cleaning of eq...

Page 18: ...and monitor heat tracing circuits The following steps show navigation of the controller s basic functions TraceNetTM Genesis CONTROL AND MONITORING SYSTEM OVERVIEW HAMBURGER MENU The Overview screen d...

Page 19: ...justments to circuit level or updates to global settings Select Global Settings to adjust how the Genesis displays system wide variables such as language temperature system time Select Import Export t...

Page 20: ...20 Appendix B Genesis Specifications Guide With Component Limits And Specifications TRACENETTM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE...

Page 21: ...r nonhazardous locations hazardous locations and Purge for hazardous locations IEC EN UL CSA 61010 1 Ex ec IIC T4 Gc II 3 Ex ec IIC T4 Gc Class I Division 2 Groups ABCD T4 Class I Zone 2 Group IIC T4...

Page 22: ...thernet USB Maximum storage temperature 85 C 185 F Minimum storage temperature 40 C 40 F Operating ambient temperature range 40 C 40 F to 70 C 158 F HMI DIMENSIONAL DATA HMI PRODUCT FEATURES TraceNet...

Page 23: ...up to 20 RTD s per circuit Monitors ground earth leakage and heater operating current in heat tracing circuits DCM COMPONENT SPECIFICATIONS Circuit control capacity up to six heat trace circuits Stor...

Page 24: ...ensors LED Identifier To Address Configurable Input Output Channels RTD Inputs DTM DIMENSIONAL DATA 41 mm 1 5 8 111 mm 4 3 8 77 mm 3 IOM INPUT OUTPUT MODULE The IOM is a DIN rail mountable input outpu...

Page 25: ...ystems communicate via Ethernet to the plant DCS The same operating data and control capabilities that are available through TraceNet Command are also accessible in the plant control room at the DCS C...

Page 26: ...puts 18 36 54 72 108 144 Distribution ND No Distribution MBx BF y z Main Breaker Breaker Frame Capacity Number of Breakers Thermon Part Number Location O Ordinary Locations H1 Class Division Hazardous...

Page 27: ...100 Thermon Dr PO Box 609 San Marcos TX 78667 0609 Phone 512 396 5801 1 800 820 4328 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Page 28: ...ide by and compare to insulation diameter charts for proper over sizing Check insulation type and thickness against design specification Replace insulation or review system design for alternate operat...

Page 29: ...emperature sensor Is RTD sensor next to pipe support equipment or other heat sink Move RTD sensor to location more representative of the majority of the piping Improperly installed RTD temperature sen...

Page 30: ...er address duplicate addresses or improper configuration of firmware software Change controller address or reconfigure firmware software Loose or open connection in RS485 line Recheck for continuity i...

Page 31: ...anticipated in the design stage Verify installed length if possible and if different review design If length is different but performance wise the as built design is acceptable initiate as built draw...

Page 32: ...ferent review design If length is different but performance wise the as built design is acceptable initiate as built drawing change and change controller low current setting Check heater set tags or m...

Page 33: ...r wiring of current sense wires through toroid The current sensing toroid must have the outgoing heater current lead and the return current heater lead run through the toroid for a proper ground leaka...

Page 34: ...0001 bit Low temperature Alarm 03 06 101 0x0065 Maintain temp 10x True Value 03 06 102 0x0066 Control Band 10x True Value 03 06 103 0x0067 High Temperature Trip Alarm 03 06 104 0x0068 High Temp Alarm...

Page 35: ...x0800 bit RTD Fault No Communication for all assigned RTD s 0x0400 bit High Temperature trip 0x0200 bit RTD Fault all assigned RTD s in fault 0x0100 bit Not Used 0x0080 bit High Current 0x0040 bit Low...

Page 36: ...ers 7171 Southwest Parkway Building 300 Suite 200 Austin TX 78735 Phone 512 690 0600 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Reviews: