background image

16

Section 4: Genesis Control Options and 

Examples

 

The TraceNet system allows a variety of control options for 

heat trace operation. 

• 

Line sensing (RTD Sensor on pipe-wall)

• 

APC (Ambient Proportional Control)

• 

Ambient Sensing (On-Off Control)

The most energy efficient control mode is to use one (or 

more) line sensing RTD’s for each heat trace circuit. When 

using this control mode, the TraceNet Genesis panel will 

have  the  RTD(s)  connected  to  the  DTM  module  in  the 

panel.

4.1: Line Sensing Control

 

When  the  RTD  is  directly  sensing  pipe-wall  surface  for 

control, the key parameters are “Maintain Temperature” at 

which the heat trace is energized or turned on. The “Max” 

temp setting is where the heat trace will be de-energized, 

or turned off. The difference between these control settings 

defines the “dead band” (aka “control differential”)
From  the  line  sensing  RTD(s)  the  temperature  of  the 

process  line  is  read  by  the  Genesis  and  is/are  also  able 

to  alarm  for  the  user’s  low  and  high  temperature  alarm 

settings.  (A  “high-high”  temperature  setting  with  circuit 

“trip”  option  is  also  determined  from  the  RTD(s)  placed 

directly on the process line.)
Line sensing is the most energy efficient method of control 

as the heat trace is only energized when the temperature 

of the line is at the “Maintain” setting (or lower) and the 

heat trace is de-energized when the it reaches the “Max” 

setting, (aka “Maintain” plus “Dead Band”.)

4.2: Ambient Sensing Options

 

 

Any ambient sensing control mode is less energy efficient 

than  line-sensing  control,  but  generally  allows  fewer 

heating circuits of longer lengths. This is because there is 

no  concern  about  process  flow  paths  for  heating  circuit 

layout, which will influence RTD placement, the number 

of sensors, and the number of heating circuits required. 
For  the  TraceNet  Genesis  system,  and  its  predecessor 

the  TCM18,  “Proportional  Control”  refers  to  a  “time 

proportioning”  function  for  saving  energy  or  more 

accurately controlling maintain temperatures. So, if a given 

situation calls for 50% power, then the controller cycles on 

and off 50% of the time to achieve this energy delivery.
There is a “Power Clamp” feature for these controllers that 

is  available  when  the  controller  is  used  with  solid-state 

relays, and is enabled when a circuit is set for “on/off with 

soft start”. This feature literally provides “soft start” using 

a reduced on/off duty time cycle of 1 second initiating at 

the percentage selected. 
There  are  two  options  for  Ambient  Sensing  with  the 

TraceNet  Genesis  System:  Ambient  Proportional  Control 

and Ambient "On-Off" Control.

4.2.1: APC (Ambient Proportional Control)

 

With  APC  the  heat  trace  will  be  set  to  operate  at  100% 

power  (continuously  on)  at  the  minimum  ambient 

temperature,  and  reduce  power  as  the  ambient 

temperature rises to the maintain temperature. When the 

ambient temperature reaches the maintain temperature, 

the  heat  trace  produces  no  heat  for  that  circuit.  This 

“Proportional  Control”  is  achieved  by  cycling  the  power 

to  the  heat  trace  “on”  and  “off”  so  the  time  “on”  is 

proportional  to  the  difference  between  the  “Maintain” 

and  ambient  temperatures.  (

Note:

  The  minimum  power 

level is 8%, so that the electrical current and earth leakage 

current levels can be accurately measured.)

Example of Ambient Proportional Control (APC):

Ma40°F (+5°C) (i.e. to keep water from freezing) in a 

minimum ambient condition of -40°F (-40°C) with APC control 

method, follow this procedure:
The “Maintain” Temperature is set at +40°F (+5°C), at which 

the heat trace would be de-energized, or “Off”.
The  “Minimum  Ambient”  temperature  (at  or  below  which 

power  is  on  100%)  would  be  programmed  to  be  a  value  of 

-40°F (-40°C). 
(Note  that  the  difference  between  the  Maintain  and  the 

Minimum  Ambient  temperature  defines  the  “Dead  Band”, 

across which the time “on” and “off” is established do deliver 

the heat proportionally. The reduced power delivery results 

in  overall  energy  consumption  when  compared  to  Ambient 

“On-Off” Control.)
APC control method can be successfully used for maintaining 

elevated temperatures as well. This can reduce the number of 

heating circuits by allowing longer heating circuits, but is not 

as energy efficient as line sensing RTD temperature control. 
The  APC  control  method  has  traditionally  been  used  only 

with Solid State control relays because of rapid cycling of the 

control relays during operation. Now, by expanding the cycle 

time between “on” and “off”, mechanical relays can be used.
“On/off with soft start” is selected with 100% Power Clamp. 

The result is that the circuit will operate in a normal on/off 

method. 

4.2.2: Ambient “On-Off” Control

In this case the heat trace is fully “on” when the ambient 

temperature falls below the “Maintain” temperature and 

is fully “off” when the ambient temperature rises above 

the “Maintain” plus the minimum control dead band.

Example of "On-Off" Ambient Sensing Control: 

As a third control mode option, the TraceNet Genesis panel 

may be configured for Ambient “On-Off” Control. In this case, 

one or two RTD’s may be used to sense ambient temperature, 

typically in a shaded area subject to wind and rain in an area 

convenient to the panel location. 
In this case, the heat trace operates at 100% power whenever 

the  ambient  temperature  drops  below  the  “Maintain” 

temperature. To winterize water lines this is typ40 to 

50°F (+5 to 10°C). If the ambient rises above this value, plus 

the minimum control dead band of +3° (°F or °C)) the heat 

trace will turn off.

Summary of Contents for Tracenet Genesis

Page 1: ...TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM Installation Operation Maintenance Guide...

Page 2: ...ts in workmanship or material under normal use and service If any part of the equipment proves to be defective in workmanship or material and if such part is within 12 months of the date of shipment f...

Page 3: ...ples 16 4 1 Line Sensing Control 16 4 2 Ambient Sensing Options 16 4 3 Proportional Control and Power Clamp 17 Section 5 Genesis Testing and Start Up 17 Section 6 Operation and Maintenance of the Gene...

Page 4: ...materials In all cases where equipment damage is observed a root cause analysis should be initiated to determine any future corrective action needed to prevent a recurrence 2 2 Wiring and Connections...

Page 5: ...response curve type is coordinated with the startup characteristic of the heat trace cable in a cold start condition All distribution wiring connections should be tightened using a torque indicating...

Page 6: ...ay but the Genesis HMI will not be able to distinguish individual circuit segments from a common control relay 3 1 3 The DTM The DTM Distributed Temperature Module is a DIN rail mountable six RTD sens...

Page 7: ...o sense 24 Vdc supplied by the IOM through an open or closed relay contact This allows input from various types of signals from 0 Vdc to 24 Vac As long as the coil side of the relay used is appropriat...

Page 8: ...move between circuits touch the circuit dot drag the black selector around the dial or use the arrows on either side of the circuit number The center of the dial displays the highlighted circuit s liv...

Page 9: ...tempting to change any setting or set point or Admin Login may be selected from the Menu Admin mode is indicated by the red tint and red boarder on and around all screens The system will remain in Adm...

Page 10: ...fault loop test and additionally turns measures heater current with heater on and off to verify relay operation and current measurements Touch to Start Mechanical Relay Duty Cycle Time Duty cycle per...

Page 11: ...e will be displayed if the measured heater current is higher than the HIGH CURRENT TRIP HIGH set point 5 HIGH CURRENT ALARM The measured heater current rise is higher than the HIGH CURRENT ALARM set p...

Page 12: ...total of Watts accumulated since last reset of value Number 0 2 147 483 648 Watts Time Heater Will Come Back On Applies to APCM time left until the heater switches on again Number 0 32 Minutes Ground...

Page 13: ...companying set point changes 3 2 8 Circuit ISO Use multi touch pinch and zoom gestures to view the ISO isometric drawing for the circuit 3 2 9 Circuit Notes Useful notes can be stored here for any pur...

Page 14: ...dual alarm or all alarms for that circuit can be acknowledged 3 2 12 Import Export The Import Export feature is used to load isometrics and to import and export system configuration files to easily an...

Page 15: ...alternate breaker and control relay it s best to have the heater reassigned to the desired breaker relay and identified at the HMI see section 3 2 6 Circuit Settings The recommended DCM code range is...

Page 16: ...h APC the heat trace will be set to operate at 100 power continuously on at the minimum ambient temperature and reduce power as the ambient temperature rises to the maintain temperature When the ambie...

Page 17: ...p Section 6 Operation and Maintenance of the Genesis Control and Monitoring System 6 1 Maintenance Preventive maintenance consists of inspection testing checking connections and general cleaning of eq...

Page 18: ...and monitor heat tracing circuits The following steps show navigation of the controller s basic functions TraceNetTM Genesis CONTROL AND MONITORING SYSTEM OVERVIEW HAMBURGER MENU The Overview screen d...

Page 19: ...justments to circuit level or updates to global settings Select Global Settings to adjust how the Genesis displays system wide variables such as language temperature system time Select Import Export t...

Page 20: ...20 Appendix B Genesis Specifications Guide With Component Limits And Specifications TRACENETTM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE...

Page 21: ...r nonhazardous locations hazardous locations and Purge for hazardous locations IEC EN UL CSA 61010 1 Ex ec IIC T4 Gc II 3 Ex ec IIC T4 Gc Class I Division 2 Groups ABCD T4 Class I Zone 2 Group IIC T4...

Page 22: ...thernet USB Maximum storage temperature 85 C 185 F Minimum storage temperature 40 C 40 F Operating ambient temperature range 40 C 40 F to 70 C 158 F HMI DIMENSIONAL DATA HMI PRODUCT FEATURES TraceNet...

Page 23: ...up to 20 RTD s per circuit Monitors ground earth leakage and heater operating current in heat tracing circuits DCM COMPONENT SPECIFICATIONS Circuit control capacity up to six heat trace circuits Stor...

Page 24: ...ensors LED Identifier To Address Configurable Input Output Channels RTD Inputs DTM DIMENSIONAL DATA 41 mm 1 5 8 111 mm 4 3 8 77 mm 3 IOM INPUT OUTPUT MODULE The IOM is a DIN rail mountable input outpu...

Page 25: ...ystems communicate via Ethernet to the plant DCS The same operating data and control capabilities that are available through TraceNet Command are also accessible in the plant control room at the DCS C...

Page 26: ...puts 18 36 54 72 108 144 Distribution ND No Distribution MBx BF y z Main Breaker Breaker Frame Capacity Number of Breakers Thermon Part Number Location O Ordinary Locations H1 Class Division Hazardous...

Page 27: ...100 Thermon Dr PO Box 609 San Marcos TX 78667 0609 Phone 512 396 5801 1 800 820 4328 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Page 28: ...ide by and compare to insulation diameter charts for proper over sizing Check insulation type and thickness against design specification Replace insulation or review system design for alternate operat...

Page 29: ...emperature sensor Is RTD sensor next to pipe support equipment or other heat sink Move RTD sensor to location more representative of the majority of the piping Improperly installed RTD temperature sen...

Page 30: ...er address duplicate addresses or improper configuration of firmware software Change controller address or reconfigure firmware software Loose or open connection in RS485 line Recheck for continuity i...

Page 31: ...anticipated in the design stage Verify installed length if possible and if different review design If length is different but performance wise the as built design is acceptable initiate as built draw...

Page 32: ...ferent review design If length is different but performance wise the as built design is acceptable initiate as built drawing change and change controller low current setting Check heater set tags or m...

Page 33: ...r wiring of current sense wires through toroid The current sensing toroid must have the outgoing heater current lead and the return current heater lead run through the toroid for a proper ground leaka...

Page 34: ...0001 bit Low temperature Alarm 03 06 101 0x0065 Maintain temp 10x True Value 03 06 102 0x0066 Control Band 10x True Value 03 06 103 0x0067 High Temperature Trip Alarm 03 06 104 0x0068 High Temp Alarm...

Page 35: ...x0800 bit RTD Fault No Communication for all assigned RTD s 0x0400 bit High Temperature trip 0x0200 bit RTD Fault all assigned RTD s in fault 0x0100 bit Not Used 0x0080 bit High Current 0x0040 bit Low...

Page 36: ...ers 7171 Southwest Parkway Building 300 Suite 200 Austin TX 78735 Phone 512 690 0600 For the Thermon office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to...

Reviews: