Manual NOVOS und thanos EVO 

 

 

 

 

 

Thermokon Sensortechnik GmbH 

 

Seite 

7

 

3

 

Assembly and commissioning 

Proper commissioning ensures a seamless and safe use of the devices. Please observe the instructions in the corresponding data sheet.

 

3.1

 

Connection 

3.1.1

 

RS485 Wiring  

The maximum cable length per line should not exceed 1,200 meters. The last device in a line must be terminated with a 120 Ohm resistor to avoid 
signal reflections from the BUS. Please make sure, that both resistors are properly connected to the terminals. The MODBUS specification requires 
the use of terminating resistors (120 - 150 Ohm, 0.25 W) at both ends.  The terminating resistor is not included in the delivery of the devices.

 

The room operating units load the BUS with a standard BUS load (1/1 unit load according to the RS485 standard). This allows up to 32 room operating 
units to be operated on one single BUS line.

 

Please also note that RS485 does NOT support star topologies and no stub line connection!

 

If no signals are present on the BUS, it must be ensured that the signal levels (voltage) are fixed. This can be done through pull-up / pull-down 
resistors on the drivers. These form a voltage divider with the installed BUS termination resistors. It must be ensured, that there is at least a 
differential voltage of 200mV detectable for the receiver between the data lines A and B.

 

3.1.2

 

Operation with alternating voltage power supply (AC) 

If several field devices are supplied from one AC voltage source according to the specification, it is mandatory, that all "positive" operating voltage 
inputs (+) of the field devices are connected to each other, and all "negative" operating voltage inputs (-) = reference potential are connected to 
each other (series connection of the field devices).

 

If the polarity of the supply voltage is reversed on one of the field devices, a short circuit of the supply voltage would occur. The short-circuit current 
thus flowing through this field device leads to a damage of this device.

 

Pay attention to a correct wiring!

 

3.1.3

 

Electrical connection 

Connect the power supply and the RS485 lines according to the wiring diagram. Power must be supplied from sources that meet the requirements 
for protective low voltage. After switching on the power supply, the device starts up.

 

 

 

 

3.2

 

RS485 BUS Configuration 

Each device that communicates through Modbus is assigned a unique address. In serial networks, only the node assigned as the Master may execute a 
command. The BUS interface can be parameterized by means of the NOVOSapp or using the onboard screen configuration menu.

 

 

 

NOVOS 7 

NOVOS Touch / thanos EVO 

Bus address 

1-247 (Address 1 – factory default) 

1/1 Bus load per device,  

corresponds to 32 participants per segment 

Baud rate 

9600 

19200 

38400 

57600 
76800 

115200 

 
 

(factory default) 

 
 

 

4800 
9600 

14400 

19200 
38400 

56000 

57600 
76800 

115200 

 
 

 

 

(factory default) 

Parity and stop bit 

Even 

Odd 

None, 1 Stop bit 

None, 2 Stop bits 

(factory default) 

 

 

|

__

DI                  

 

Digital Input 

(für potentialfreien Kontakt → GND)

 

|

__

B- 

____________ 

BUS B 

|

__

B- 

____________ 

BUS B 

|

__

A+

____________ 

BUS A 

|

__

A+

____________ 

BUS A 

|

__

GND

_________

 0 V

 

|

__

UB+

__________

 24 V 

 (±10%) / 24 V 

 (±10%) SELV 

 

Summary of Contents for NOVOS 3

Page 1: ...Thermokon Sensortechnik GmbH www thermokon de email thermokon de Operating Manual NOVOS 7 NOVOS Touch thanos EVO RS485 Modbus Register Specification NOVOS 3 NOVOS 5 NOVOS 7 NOVOS Touch thanos EVO...

Page 2: ...and Lighting added DF SW Ver 1 4 0 Colorpicker added only NOVOS Touch thanos EVO New icons for curtains shading added Screen lock added individual logo for bootscreen homescreen and screensaver possi...

Page 3: ...3 1 3 Electrical connection 7 3 2 RS485 BUS Configuration 7 3 3 Configuration 8 3 4 Structure of the variables Data blocks of Modbus Register 8 4 Display and operation 8 4 1 Display and operating ele...

Page 4: ...on data block Climate 31 6 5 Configuration data block Lighting 33 6 6 Configuration data block Shading 37 6 7 Configuration data block Scenes 41 6 8 Configuration data block Sensors 42 6 9 Configurati...

Page 5: ...d use The device is intended for use in an RS485 network The room control unit is intended for use in offices meeting or conference rooms hotels reception lobby areas nursing homes and hospitals and g...

Page 6: ...different sensors temperature relative humidity CO2 and VOC Intuitive and comfortable control of room climate Call up ECO mode for energy savings and a sustainable climate control Green Leaf Control o...

Page 7: ...voltage source according to the specification it is mandatory that all positive operating voltage inputs of the field devices are connected to each other and all negative operating voltage inputs refe...

Page 8: ...lding management System BMS using the RS485 Modbus network 3 4 Structure of the variables Data blocks of Modbus Register The parameters are split into two main groups the configuration parameters and...

Page 9: ...Room occupancy occupied unoccupied Description see ECO function ECO function Icon ON OFF or user interaction The room occupancy and ECO function are triggered on the device via toggle button NOVOS 7 D...

Page 10: ...ress 402 53 HEX S Address 403 54 HEX T Time and Date Time and date can be shown or hidden independently of each other The date formats DD MM YYYY or MM DD YYYY and the time formats 24h or 12h AM PM ar...

Page 11: ...ivery and the step width of the adjustment is 0 5K All the above settings can certainly be configured as required In conjunction with the heating and cooling icons in the header the set point can also...

Page 12: ...button 1 is pressed in standby or on the home screen the respective function is triggered and the corresponding symbol is displayed on the home screen for approx 3 seconds Favorite buttons NOVOS Touc...

Page 13: ...played as buttons The activation of the ECO mode switching of room occupancy and the submenu for fan speed adjustment are arranged in the Climate menu unlike the NOVOS 7 To activate or deactivate the...

Page 14: ...nt ECO mode and room occupancy are an integral part of the air conditioning AC menu ECO mode and room assignment are activated or deactivated directly through the toggle button When the button for the...

Page 15: ...e dimming value can be set by the user with the rotary push button in the respective sub menu of the lighting group If dimming is configured as push button mode instead of the slider bar the percentag...

Page 16: ...mmands and In that case a short or long key press is shown in the respective register After the register has been read it will automatically be reset to NoPress Non dimmable lights are switched on or...

Page 17: ...1552 Min light color 4 Data address 1553 Max light color 4 Data address 1554 Min light color 5 Data address 1555 Max light color 5 Data address 1556 Min light color 6 Data address 1557 Max light colo...

Page 18: ...shutter 3 Roller shutter group 4 Curtain 5 Curtain group Shading groups Just like the lighting groups up to eight shading circuits can be controlled The shading menu is available in the NOVOS 7 NOVOS...

Page 19: ...sed on the logic of a traffic light Using freely selectable threshold values the individual measured values can be clearly highlighted with freely selectable colors In the background of the button a l...

Page 20: ...on menu offers the possibility to change the interface parameters date and time as well as offsets of the measured values Additional information such as hardware or software versions can also be calle...

Page 21: ...provided in favourite register 2 Parameter Description N3 N5 N7 Touch EVO Min Max Default Access Data address Favourite 0 Assignment see register 5000 0 Favourite 1 Assignment see register 5001 1 Fav...

Page 22: ...int16_t 103 Fan stage internal Fan stage set by the user 0 OFF 1 Stage 1 2 Stage 2 3 Stage 3 4 Stage 4 5 Stage 5 6 Auto 0 6 Reset value N7 Touch EVO r uint16_t 104 Fan stage Feedback from BMS Overwrit...

Page 23: ...UTO Mode for Lighting 1 8 Summary of coils 32 39 If individual lighting circuits are to be controlled temporarily exclusively by the BMS the buttons for setting individual lighting circuits can be dis...

Page 24: ...g status 1 0 116 0 r w uint16_t 306 Slat adjustment Blind 4 Description see Slat adjustment 1 180 180 0 r w uint16_t 307 Shading status 5 Description see Shading status 1 0 116 0 r w uint16_t 308 Slat...

Page 25: ...through BMS 0 not active 1 active 0 1 0 r w 424 Force a restart Software reset Device is reset to configured settings volatile data is reset software reset 0 not active 1 active 0 1 0 r w 425 LED ON...

Page 26: ...t16_t 505 VOC Configuration of the sensor parameters see Register block 2610 ff r int16_t 506 CO2 VOC MIX Configuration of the sensor parameters see Register block 2710 ff r int16_t 507 ext Sensor 1 C...

Page 27: ...tion date Month Day Is written during calibration of the base PCB hexadecimal MMDD 0 r w uint16_t 1030 Production date Year Is written during calibration of the base PCB hexadecimal YYYY uint16_t 1031...

Page 28: ...uint16_t 1109 Time Minute 0 59 0 r w uint16_t 1110 Time Second 0 59 0 r w uint16_t 1111 Definition long button push Threshold value where a button push is interpreted as a short or long push x millis...

Page 29: ...6_t 1117 Favourite button 2 see Favourite button 1 1 r w uint16_t 1118 Favourite button 3 see Favourite button 1 2 r w uint16_t 1119 Favourite button 4 see Favourite button 1 9 r w uint16_t 1120 Favou...

Page 30: ...15 r w uint16_t 1204 Button standby Display ON OFF Show hide menu button for standby Touch EVO menu incl cleaning mode 0 no 1 yes 0 1 1 r w uint16_t 1205 Measured values display Measured values are sh...

Page 31: ...etpoint adjustment 1 0 1 5 0 5 10 1 0 0 50 5 r w uint16_t 1304 ECO button Display ON OFF Display ECO button menu bar and temperature menu 0 no 1 yes 1 Only NOVOS 7 2 yes climate menu and carousel In E...

Page 32: ..._t 1310 Minimum Fan Stage Minimum selectable Fan stage 0 0 1 1 2 2 3 3 4 4 5 5 0 5 0 r w uint16 _t 1311 Fan Stage after power reset Preset Fan Stage after power reset 0 OFF 1 Stage 1 2 Stage 2 3 Stage...

Page 33: ...its Number of adjustable lighting circuits 0 8 0 8 8 r w 1401 Graphical representation of the lighting circuits With NOVOS Touch and thanos EVO this function can be displayed via the corresponding sub...

Page 34: ...is principle is only suitable for fast BUS topologies With high latency times it may happen that button commands are not recognized due to high latencies RYB Color picker Only Novos Touch and thanos E...

Page 35: ...ighting 2 Coordinate X Description see Lighting 1 0 960 0 r w 1437 Lighting 2 Coordinate Y Description see Lighting 1 0 800 0 r w 1438 Lighting 3 Description Description see Lighting 1 Light 3 r w 143...

Page 36: ...t Description see Lighting 1 0 2 0 r w 1524 Lighting 7 Dimmable Description see Lighting 1 0 1 1 r w 1525 Lighting 7 Dimming interval Description see Lighting 1 0 100 5 r w 1526 Lighting 7 Coordinate...

Page 37: ...1 Roller shutter 2 Roller shutter group 3 Curtain 4 Curtain group 5 0 105 0 r w 1615 Shading 1 Adjustment GUI For shading systems there are different possibilities to adjust the level Slider Slider f...

Page 38: ...w 1637 Shading 2 Blade adjustment Description see Shading 1 1 yes r w 1638 Shading 2 Slat angle position min Description see Shading 1 80 r w 1639 Shading 2 Slat angle position max Description see Sh...

Page 39: ...ion adjustment Description see Shading 1 1 r w 1701 Shading 5 Slat angle position min Description see Shading 1 80 r w 1702 Shading 5 Slat angle position max Description see Shading 1 80 r w 1703 Shad...

Page 40: ...10 r w 1747 Shading 8 Coordinate X Description see Shading 1 0 r w 1748 Shading 8 Coordinate Y Description see Shading 1 0 r w 1749 Shading 8 Description Description see Shading 1 Blind 8 r w 1750 Sh...

Page 41: ...Description Scene 2 Description see Scene 1 Scene 2 r w 1815 Icon Scene 2 Description see Scene 1 0 105 8 r w 1827 Description Scene 3 Description see Scene 1 Scene 3 r w 1828 Icon Scene 3 Descriptio...

Page 42: ...4 2736 2749 External Sensor 1 2809 ff 2810 2824 2836 2849 Version 1 4 NOVOS 7 Touch thanos EVO Overwrite external value 1 Data address 2809 Overwrite external value 2 Data address 2909 Overwrite exter...

Page 43: ...affic Light Function The colour thresholds can be adjusted individually 0 not active 1 active with TLF w o 60 min chart 2 active w o TLF with 60 min chart 3 active with TLF with 60 min chart 4 active...

Page 44: ...n measuring range limits 230 r w int16_t 2023 Threshold value 4 5 Threshold value between range 4 and range 5 Absolute value within measuring range limits 260 r w int16_t 2024 Sensor Icon Selection of...

Page 45: ...Favourite 10 5010 Configuration Favourite 11 5011 Configuration Favourite 12 5012 Configuration Favourite 13 5013 Configuration Favourite 14 5014 Configuration Favourite 15 5015 Configuration Favouri...

Page 46: ...ting 7 Coil for Lighting ON OFF OFF 0 ON 1 r w 6 0 Status Lighting 8 Coil for Lighting ON OFF OFF 0 ON 1 r w 7 0 7 2 Coil data block Scenes The states of the coils for lighting and scenes are summaris...

Page 47: ...active 1 active r w 19 0 Show USB Communication mode Icon Coil Register for icon ON OFF Activated automatically when USB connection is active 0 not active 1 active r w 20 0 Show ECO Icon Coil Registe...

Page 48: ...7 Coil for AUTO Mode ON OFF 0 not active 1 active r w 38 0 AUTO Mode Lighting 8 Coil for AUTO Mode ON OFF 0 not active 1 active r w 39 0 7 5 Coil data block AUTO Mode for Shading 1 8 The states of th...

Page 49: ...ls available for 24 actions value changes Parameter Description N3 N5 N7 Touch EVO Min Max Default Access Data address Configuration Time channel 1 Hour 0 23 r w uint16_t 6000 Minute 0 59 r w uint16_t...

Page 50: ...racters Table name Hexadecimal implemented Decimal implemented Original Unicode Latin Basic 0x0020 0x007F 20 127 unicode org PDF Latin supplement 0x0080 0x00FF 128 255 unicode org PDF Latin extension...

Page 51: ...aves are connected to the serial BUS The communication between Master and Slave is solely controlled by the Master Slaves are only allowed to send if they were called by the Master before Slaves are o...

Page 52: ...the checksum received If the values are not matching a transmission error must be assumed and the data received are rejected The low order byte of the 16 bit checksum is sent in the telegram in the n...

Page 53: ...Manual NOVOS und thanos EVO Thermokon Sensortechnik GmbH Seite 53 Thermokon Sensortechnik GmbH Platanenweg 1 35756 Mittenaar Offenbach Deutschland www thermokon de...

Reviews: