Manual NOVOS und thanos EVO
Seite
28
Thermokon Sensortechnik GmbH
6.2
Configuration data block “General”
Parameter
Description
N3
N5
N7
Touch/
EVO
Min
Max
Default
Access
Data
address
Measuring system
Change of the measurement unit
system
1 = SI
2 = Imp
●
●
●
●
1
2
1
r / w
uint16_t
1100
Language
Setting the language
1 = German
2 = English
7 = Czech
9 = Russian
●
●
1
2
2
r / w
uint16_t
1101
Format Date
Setting the date format
0 = OFF
1 = DD.MM.YY
2 = YY.MM.DD
●
●
0
2
1
r / w
uint16_t
1104
Time format
Setting the time format
0 = OFF
1 = 12h (am/pm)
2 = 24h
●
●
0
2
2
r / w
uint16_t
1105
Date Year
Setting the date
YYYY
MM
DD
●
●
2000
2099
2019
r / w
uint16_t
1106
Date Month
●
●
1
12
1
r / w
uint16_t
1107
Date Day
●
●
1
31
1
r / w
uint16_t
1108
Time Hour
Setting the time
HH
MM
SS
●
●
0
23
12
r / w
uint16_t
1109
Time Minute
●
●
0
59
0
r / w
uint16_t
1110
Time Second
●
●
0
59
0
r / w
uint16_t
1111
Definition “long” button
push
Threshold value where a button push
is interpreted as a short or long push
x milliseconds
●
●
250
5000
700
r / w
uint16_t
1112
Maintenance countdown
Hourly value Default: 24 months /
Counts down every hour. If the value
is 0, maintenance is recommended.
●
●
●
●
0
65535
0
r / w
uint16_t
1113
Calibration countdown
Hourly value Default: 24 months /
Counts down every hour. If the value
is 0, calibration is recommended.
●
●
●
●
0
65535
0
r / w
uint16_t
1114
Maintenance interval
Factory default setting
0 = Maintenance deactivated
(Icon not
active after countdown expire, at
value >0, icon active after countdown
expire)
0 … 48 Months
●
●
●
●
0
48
0
r / w
uint16_t
1115
Calibration interval
Factory default setting
0 = Calibration deactivated
(Icon not
active after countdown expire, at
value >0, icon active after countdown
expire)
0 … 48 Months
●
●
●
●
0
48
0
r / w
uint16_t
1116