Manual NOVOS und thanos EVO
Thermokon Sensortechnik GmbH
Seite
25
5.5
Data block “Status display and special functions”
Parameter
Description
N3
N5
N7
Touch/
EVO
Min
Max
Default Access
Data
address
Status report
Message is displayed in the Home
screen.
Max. 24 characters. Not defined by
default. One character in Unicode
format per register.
Register 400..423
●
●
r / w
400..423
Display OFF
Display is switched off automatically.
The display wakes up again at the next
user interaction. Alternatively, the
display can be re-activated through
BMS.
0 = not active
1 = active
●
●
0
1
0
r / w
424
Force a restart
(Software reset)
Device is reset to configured settings
(volatile data is reset = software reset)
0 = not active
1 = active
●
●
0
1
0
r / w
425
LED ON/OFF
The LED can be switched OFF / ON
directly using the values 0 or 1.
Alternatively, it can be switched OFF/ON
on when the button gets pressed (value
= 2).
0 = not active
1 = active
2 = Room occupancy /
Button status
●
●
0
2
0
r / w
426
LED colour
The colour of the LED can be changed by
the BMS in this register.
0 = transparent
1 = white
2 = black
3 = red
4 = green
5 = blue
6 = yellow
7 = magenta
8 = turquoise
●
●
0
8
4
r / w
427
Piezo-Summer Frequenz
Tonfrequenz 0-15.000 Hz
●
●
0
15.000
r / w
428
Piezo-Summer Tondauer
Tondauer 0-65.535 Sekunden
●
●
0
65.535
r / w
429