Manual NOVOS und thanos EVO
Thermokon Sensortechnik GmbH
Seite
37
6.6
Configuration data block “Shading”
Parameter
Description
N3
N5
N7
Touch/
EVO
Min
Max
Default Access
Data
address
Display shading menu
(Display ON/OFF)
Display “Shading” menu in the
menu bar
0 = no
1 = yes
●
●
0
1
1
r / w
1600
Number of Shading circuits
Number of adjustable shading
circuits
1…8
●
●
0
8
8
r / w
1601
Graphical representation of
the Shading circuits
With NOVOS Touch and thanos
EVO, this function can be displayed
via the corresponding submenu
and/or via a 2D room graphic
0 = List view
1 = 2D Floor plan view
2 = both
●
0
2
0
1602
Shading 1 - Description
Description for the first Shading
circuit
Max. 12 characters. One character
in Unicode format per register.
●
●
Blind 1
r / w
1603..1614
Shading 1 – Icon
Selection of the icon
for Shading 1
Blind = 0
Blind group = 1
Roller shutter = 2
Roller shutter group= 3
Curtain = 4
Curtain group = 5
●
●
0
105
0
r / w
1615
Shading 1 – Adjustment GUI
For shading systems there are
different possibilities to adjust the
level
Slider: Slider for vertical shading
systems. Adjustment of the
position is done through a slider
bar.
Push button operation: NOVOS
evaluates whether a long or short
button push for up or down is
actuated. After the read operation,
the value in register X must be
reset by the BMS to “
not pressed
”.
Push button operation (raw): In
register X the command for up /
down is performed as long as the
button is pressed. After releasing
the button, the value automatically
switches back to “
not pressed
”.
This principle is only suitable for
fast BUS topologies. In case of high
latency times, it may well happen
that button commands are not
recognized due to the high
latencies.
Slider horizontal: Slider for curtains
0 = Slider vertical (Blinds)
1 = Push button operation
2 = Push button operation (raw)
3 = Slider horizontal (Curtain)
●
●
0
2
0
r / w
1616
0
1
2
3
4
5